163
-
E1
Remote controller
communication circuit error
.HHSVÀDVKLQJ
Stays OFF
.HHSVÀDVKLQJ
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the
power reset?
Does the drain
pump restart automatically
1 minute later?
Turn SW7-1 to OFF.
ON
Remove the wire
connecting
between indoor/outdoor units.
YES
YES
NO
Note (2) Does the remote controller still display “ ” even
after 3 minutes?
Power reset
NO
WAIT
Malfunction by noise
Check peripheral
environment.
Defective indoor control
PCB
ª
Replace.
Defective remote controller
ª
Replace.
2. Error detection method
When normal communication
between the remote controller
and the indoor unit is
interrupted for more than 2
minutes. (Detectable only with
the remote controller)
3. Condition of Error displayed
Same as above
4. Presumable cause
• Defective communication
circuit between remote
controller-indoor unit
• Noise
• Defective remote controller
• Faulty indoor control PCB
Note:
If the indoor unit cannot communicate normally with the remote controller for 180 seconds, the indoor unit PCB starts to
reset automatically.
Error code
Remote controller:
L
ED
G
reen
Red
Indoor
Outdoor
Content
'11 • PAC-T-160