-
100
-
'11 • PAC-T-160
(c)
Compressor soft start control
1)
Compressor protection start I
[Control condition] Normally, the compressor operation frequency is raised in this start pattern.
[Control contents]
a) Starts with the compressor’s target frequency at
A
rps.
However, when the ambient air temperature (Tho-A) is 35°C or higher during cooling/
dehumidifying or the indoor return air temperature (Th
I
-A) is 25°C or higher during heating, it
starts at
C
rps.
b) At 30 seconds after the start of compressor, its target frequency changes to
B
rps and the
compressor is operated for 2 - 4 minutes with its operation frequency fixed at
B
rps.
Model
Operation mode
A rps
B rps
C rps
100~140
Cooling/Dehumidifying
55
55
30
Heating
55
55
30
200, 250
Cooling/Dehumidifying
55
55
30
Heating
55
55
30
2)
Compressor protection start III
[Control condition] Number of compressor starts is only 1 counted after the power supply breaker ON.
[Control contents]
Operates by selecting one of following start patterns according to the operation mode and the
outdoor air temperature (Tho-A).
a)
Low frequency operation control during cooling/dehumidifying
[Control condition] Upon establishing the conditions of compressor protection start III, the low frequency
operation control is performed during cooling/dehumidifying.
[Control contents]
Starts with the compressor’s target frequency at
A
rps. When the outdoor air temperature
(Tho-A) is 35°C or higher, it starts at
C
rps.
At 30 seconds after the compressor start, the compressor’s target frequency is changed to
B
rps and the compressor’s operation frequency is fixed for 10 minutes.
Model
Operation mode
A rps
B rps
C rps
100~140
Cooling/Dehumidifying
55
55
30
200, 250
Cooling/Dehumidifying
55
30
30
b)
Low frequency operation control during heating
[Control condition] When the conditions of compressor protection start III are established and one of following conditions
and
is satisfied, the low number of revolutions operation control is performed during heating.
At 30 minutes or more after turning the power supply breaker on
Compressor underneath temperature (Tho-H) is 4°C or higher and the difference from the
outdoor air temperature (Tho-A) becomes 4°C or higher. [model 200, 250 only]
[Control contents]
Starts the compressor with its target frequency at
A
rps. However, when the indoor unit
return air temperature (Th
I
-A) is 25°C or higher, it start at
C
rps.
At 30 seconds after the start of compressor, the compressor’s target frequency is changed to
B
rps and the compressor’s operation frequency is fixed for 10 minutes.
Model
Operation mode
A rps
B rps
C rps
100~140
Heating
55
55
30
200, 250
Heating
55
30
30
Summary of Contents for FDC100VNA
Page 81: ... 80 80 11 PAC T 160 ...
Page 82: ... 81 81 11 PAC T 160 ...
Page 83: ... 82 82 11 PAC T 160 ...