112
-
'11 • PAC-T-160
(4) Outdoor unit fan control
(a) Outdoor unit fan tap and fan motor speed
Unit: min
-1
Model
Mode
Fan motor tap
71
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
400
600
710
810
850
950
Heating
200
400
600
710
810
850
950
100
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
350
600
740
820
870
950
Heating
200
350
600
740
820
870
950
125, 140
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
370
560
640
745
870
910
Heating
200
370
560
640
800
870
910
(b) Fan tap control during cooling/heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
zone
zone
zone
zone
zone
Tap 5(6)
Tap 5(6)
Tap 5(6)
Tap 4
zone
Tap 5(6)
Tap 5(6)
Tap 4(6)
Tap 3
zone
Tap 4
Tap 4
Tap 3
Tap 2
zone
Tap 3
Tap 3
Tap 2
Tap 1
Note (1) Value in ( ) is for the model 71.
zone
zone
Outdoor air temp. (˚C)
15
18
zone
30
37
zone
46
48
zone
Outdoor unit heat exchanger temp. (˚C)
20
30
zone
33
40
zone
43
53
zone
(c) Fan tap control during heating operation
Fan taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
zone
zone
zone
zone
Tap 3
Tap 3
Tap 4
zone
Tap 3
Tap 4(5)
Tap 5
zone
Tap 4
Tap 5
Tap 6
Note (1) Value in (
) is for the model 71.
3
9
12
15
-2
0
1
3
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
zone
zone
zone
zone
zone
zone
(d) Outdoor unit fan control at cooling low outdoor air
1) When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone
in the cooling/dehumidifying mode, it has elapsed 20
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
5
10
Retained
Outdoor unit fan speed
-10min
-1
20
30
Outdoor unit fan speed
+10min
-1
zone
zone
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)