184
–
'11 • PAC-T-160
Error code
Remote controller:
L
ED
G
reen
Red
Outdoor
Content
Keeps flashing 1 time flash
Indoor Keeps flashing Stays OFF
E45
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Correct the connection
Set JSW10, 11(SW1, 2)
correctly
No power is supplied to
inverter PCB
Check the power supply
voltage and correct it
Replace outdoor fan motor
Replace control PCB
if not solved, replace
INV PCB as well
Connect the communication
wire securely
Replace inverter PCB
OK
2. Error detection method
When the communication
between inverter PCB and
outdoor control PCB is not
established.
3. Condition of Error displayed
Same as above.
4. Presumable cause
Note:
Communication error between
inverter PCB and outdoor control PCB
• Inverter PCB anomaly
• Anomalous connection of
connector between
inverter PCB and outdoor
control PCB
• Outdoor control PCB anomaly
• Outdoor fan motor anomaly
YES
NO
NO
YES
Are both
switches of JSW10,11(SW1, 2)
on the inverter PCB
set correctly?
NO
YES
Is the
connection of connectors between
the inverter PCB and the outdoor
control
PCB OK?
NO
YES
Is the
communication wire between the
inverter PCB and the outdoor control
PCB connected properly ?
Replace the outdoor control PCB
(1)
Note (1): Figure in ( ) are for model 200, 250
Is 15VDC
detected between
and
on CNI3?
NO
YES
Is 15VDC
detected after disconnecting
outdoor fan motor?
YES
NO
Note (2): For model 200 &
250, check during test run
operation.
(2)
For 3-phase models
(4)
(4)
Does it become normal?
Is LED
on the inverter PCB
flashing ?
NO
YES
For single-phase models
Note (4): Under anomalous conditions,
the voltage becomes less than 14VDC
(3)
Note (3):
How to check
voltage at CN13
See E51
Ј
,IQRWVROYHG¿QGWKHFDXVH
by checking following points.
• Fan motor anomaly
• 52X anomaly (model 200, 250 only)
•
%URNHQFHPHQWUHVLVWRUȍ
(model 200, 250 only)