194
–
'11 • PAC-T-160
E59
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Check the power supply
voltage and correct it
Replace inverter PCB
If not solved yet, replace
1RLVH¿OWHU3&%
Replace outdoorfan motor
OK
Check refrigerant amount
and refrigerant circuit
Replace compressor
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
(If the compressor speed cannot
increase 11Hz or higher)
3. Condition of Error displayed
If the compressor fails to startup for
20 times (10 patterns x 2 times)
continuously.
4. Presumable cause
Note : Insulation resistance
7KHXQLWLVOHIWIRUORQJSHULRGZLWKRXWSRZHUVXSSO\RUVRRQDIWHULQVWDOODWLRQLQVXODWLRQUHVLVWDQFHPD\GHFUHDVHWRVHYHUDO0ȍRUORZHU
due to the liquid refrigerant migrated in the refrigerant oil in compressor. If the electric leakage breaker is activated due to low insulation
resistance, check followings.
Check whether the insulation resistance can recover or not, after 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated)
&KHFNZKHWKHUWKHHOHFWULFOHDNDJHEUHDNHUFRQIRUPVWRKLJKKDUPRQLFVSHFL¿FDWLRQV
(As INV PAC units has inverter, in order to prevent from improper operation, be sure to use the breaker of high-harmonic type)
Error code
Remote controller:
L
ED
G
reen
Red
Outdoor control PCB
Outdoor
inverter
PCB
1 time flash
Keeps flashing
Yellow or Red L
ED
G
reen
Indoor control PCB
Stays OFF
Keeps flashing
Keeps flashing
Content
Stays off or 4 times flash
Compressor startup failure (1/2)
• Outdoor fan motor anomaly
• Outdoor control PCB anomaly
• Inverter PCB anomaly
• Anomalous power supply
voltage
• Insufficient or Excessive
refrigerant amount
• Faulty component for
refrigerant circuit
• Compressor anomaly
(Motor or bearing)
To next page
Is DC15V
detected after disconnecting
outdoor fan motor?
In case that the compressor
does not start at all and no
sound or vibration exists
Is
power supply voltage
OK?
Is the
insulation resistance
and coil resistance of
compressor OK?
Is the
pressure equalized
at starting OK?
Is DC15V
detected between
and
on CNI3?
A
For Single phase models
For
3 phase models
Note (2): Under anomalous conditions,
the voltage becomes less than 14VDC
(2)
(2)
Replace control PCB
Can compressor
startup?
Note (1): How to check voltage
at CN13 See E51
(1)
Ј
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
YES
YES
Summary of Contents for FDC100VNA