'11 • PAC-T-160
11.2 Troubleshooting flow
(1)
List of troubles
Remote controller display
Description of trouble
Reference page
None
Operates but does not cool.
149
None
Operates but does not heat.
150
None
Earth leakage breaker activated
151
None
Excessive noise/vibration (1/3)
152
None
Excessive noise/vibration (2/3)
153
None
Excessive noise/vibration (3/3)
154
None
Power supply system error (Power supply to indoor control PCB)
155
None
Power supply system error (Power supply to remote controller)
156
INSPECT I/U
INSPECT I/U (When 1 or 2 remote controllers are connected)
157
INSPECT I/U
INSPECT I/U (Connection of 3 units or more remote controllers)
158
WAIT
Communication error at initial operation
159
〜
161
None
No display
162
E1
Remote controller communication circuit error
163
E5
Communication error during operation
164
E6
Indoor heat exchanger temperature thermistor anomaly
165
E7
Return air temperature thermistor anomaly
166
E8
Heating overload operation
167
E10
Excessive number of connected indoor units (more than 17 units) by controlling with one remote controller
168
E14
Communication error between master and slave indoor units
169
E16
Indoor fan motor anomaly
170
E19
Indoor unit operation check
171
E20
Indoor fan motor rotation speed anomaly
172
E28
Remote controller temperature thermistor anomaly
173
E35
Cooling overload operation
174
E36
Discharge pipe temperature error
175
E37
Outdoor heat exchanger temperature thermistor anomaly
176
E38
Outdoor air temperature thermistor anomaly
177
E39
Discharge pipe temperature thermistor anomaly
178
E40
High pressure error (63H1 activated)
179
E41
Power transistor overheat
180, 181
E42
Current cut
182, 183
E45
Communication error between inverter PCB and outdoor control PCB
184
E47
Inverter PCB A/F module anomaly (Model FDC 71 only)
185
E48
Outdoor fan motor anomaly
186
E49
Low pressure error or low pressure sensor anomaly
187, 188
E51
Inverter and fan motor anomaly
189
E53
Suction pipe temperature thermistor anomaly
190
E54
Low pressure sensor anomaly
191
E55
Underneath temperature thermistor anomaly (Models FDC 200, 250 only)
192
E57
Insufficient refrigerant amount or detection of service valve closure
193
E59
Compressor startup failure
194, 195
E60
Compressor rotor lock error (Models FDC 200, 250 only)
196