3 - 35
3. SIGNALS AND WIRING
(2) For 1-phase 230VAC power supply
1-phase 230VAC
Emergency stop
Servo-on
Servo amplifier
Trouble
Emergency
stop
External
power
supply
24VDC
RA
OFF
ON
MC
MC
SK
NFB
MC
L
1
L
2
L
3
EMG
SON
VIN
VIN
ALM
SG
RA
(Note)
CNP1
P
D
C
Note. To use the built-in regenerative resistor, be sure to connect across P and D of the power supply connector (CNP1).
3.7.2 Terminals
Refer to section 11.1 (4) for the signal arrangement.
Connected terminal
(Application)
Symbol Description
Supply L
1
, L
2
and L
3
with the following power.
For 1-phase 230VAC, connect the power supply to L
1
, L
2
and L
3
open.
L
1
Servo amplifier
Power supply
MR-E-10A-QW003 to
MR-E-70A-QW003
MR-E-100A-QW003/
MR-E-200A-QW003
L
2
3-phase 200 to 230VAC,
50/60Hz
L
1
L
2
L
3
1-phase 230VAC,
50/60Hz
L
1
L
2
Power supply
L
3
U
V
Servo motor
W
Connect to the servo motor power terminals (U, V, W). During power-on, do not open
or close the motor power line. Otherwise, a malfunction or faulty may occur.
P
C
Regenerative option
D
To use the built-in regenerative resistor of the servo amplifier, connect the wiring across
P-D of the power supply connector (CNP1).
When using the regenerative option, always remove the wiring from across P-D and
connect the regenerative option across P-C.
Refer to section 13.1.1 for details.
Protective earth (PE)
Connect this terminal to the protective earth (PE) terminals of the servo motor and
control box for grounding.
www.DataSheet4U.com
Summary of Contents for EZMOTION MR-E Super MR-E-10A-QW003
Page 17: ...6 MEMO www DataSheet4U com ...
Page 31: ...2 4 2 INSTALLATION MEMO www DataSheet4U com ...
Page 85: ...4 6 4 OPERATION MEMO www DataSheet4U com ...
Page 115: ...5 30 5 PARAMETERS MEMO www DataSheet4U com ...
Page 149: ...8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO www DataSheet4U com ...
Page 163: ...10 12 10 TROUBLESHOOTING MEMO www DataSheet4U com ...