6 - 13
6. DISPLAY AND OPERATION
6.8.3 Positioning operation
POINT
The MR Configurator (servo configuration software) is required to perform
positioning operation.
Positioning operation can be performed once when there is no command from the external command device.
(1) Operation
Connect EMG-VIN to start positioning operation to use the internal power supply.
Click the "Forward" or "Reverse" button on the MR Configurator (servo configuration software) starts the
servo motor, which will then stop after moving the preset travel distance. You can change the operation
conditions on the MR Configurator (servo configuration software). The initial conditions and setting ranges
for operation are listed below.
Item
Initial setting
Setting range
Travel distance [pulse]
10000
0 to 9999999
Speed [r/min]
200
0 to instantaneous permissible speed
Acceleration/deceleration time constant [ms]
1000
0 to 50000
How to use the buttons is explained below.
Button Description
"Forward"
Click to start positioning operation CCW.
"Reverse"
Click to start positioning operation CW.
"Pause"
Click during operation to make a temporary stop. Pressing the "Pause" button again erases the
remaining distance.
To resume operation, click the button that was clicked to start the operation.
If the communication cable is disconnected during positioning operation, the servo motor will come to a
sudden stop.
(2) Status display
You can monitor the status display even during positioning operation.
www.DataSheet4U.com
Summary of Contents for EZMOTION MR-E Super MR-E-10A-QW003
Page 17: ...6 MEMO www DataSheet4U com ...
Page 31: ...2 4 2 INSTALLATION MEMO www DataSheet4U com ...
Page 85: ...4 6 4 OPERATION MEMO www DataSheet4U com ...
Page 115: ...5 30 5 PARAMETERS MEMO www DataSheet4U com ...
Page 149: ...8 10 8 SPECIAL ADJUSTMENT FUNCTIONS MEMO www DataSheet4U com ...
Page 163: ...10 12 10 TROUBLESHOOTING MEMO www DataSheet4U com ...