- 16 -
4. Accessories
(1) PWFY
(A) Strainer
(B) Heat insulation material
*1
*2
*2
*2
*1. PWFY-P100VM-E-BU only
*2. PWFY-EP100VM-E1/E2-AU only
(C) Expansion joint 2
(D) Wire
(E) Flow switch
(F) Buffer material
(A) Install the strainer at the water pipe inlet.
(B) This insulation is for exclusive use with the strainer. Wrap the strainer with the insulation after water pipes are
installed.
(C) Install them at the strainer inlet. Refer to P49 for details.
(D) To perform test run before the pump interlock circuit is completed, short circuit the terminal block TB142A (IN1),
and then perform test run.
(E) When installing the unit, be sure to install the supplied flow switch on the water outlet side of the unit and connect the
wire to IN1 of TB142A on the unit.
(F) If allowing wires inside the unit to hang loosely so as to prevent water from collecting and running down into electrical
components, be careful not to let the wires hang so loosely as to come into contact with nearby piping (solenoid
valves). If there is any risk of contact being made, use the included buffer material to protect other components.
(2) CMB-P104V-G1
SIZE
Unit
ODø19.05 - IDø15.88
1
ODø22.2 - IDø19.05
1
ODø22.2 - IDø28.6
1
Drain hose set
1set
Installation Manual
1
(3) CMB-PW202V-J
SIZE
Unit
ODø19.05 - IDø15.88
2
ODø22.2 - IDø19.05
1
ODø15.88 - IDø9.52
1
ODø15.88 - IDø12.7
1
ODø25.4 - IDø19.05
1
ODø25.4 - IDø22.2
1
ODø19.05 - IDø22.2
1
ODø25.4 - IDø28.6
1
ODø22.2 - IDø28.6
1
ODø25.4 - IDø15.88
1
Drain hose set
1 set
Installation Manual