- 1 -
1. Unit configuration table
Model
PWFY-P100VM-E-BU
PWFY-EP100VM-E1-AU
PWFY-EP100VM-E2-AU
Outdoor unit
(Heat source unit for WY,
WR2 series)
R2 series, WR2 series only
Y series, HP (ZUBADAN) series,
WY series, R2, WR2 series
Connection
BC controller
BC controller: CMB-P104,105,106,108,1010,1013,1016V-G1
Main BC controller: CMB-P108,1010,1013,1016V-GA1 / CMB-P1016V-HA1
Sub BC controller: CMB-P104,108V-GB1 / CMB-P1016V-HB1
WCB
CMB-PW202V-J
2. Operable temperature range
<PWFY-P100VM-E-BU>
Only PWFY
PWFY with
standard indoor unit
Only standard
indoor units
Heating
Inlet water temperature
R2/WR2 series
10 to 70ºC
10 to 70ºC
–
Outdoor temperature
R2 series
-20 to 32ºCWB
-20 to 32ºCWB
-20 to 15.5ºCWB
Circulating water
temperature WR2 series
10 to 45ºC
10 to 45ºC
10 to 45ºC
<PWFY-EP100VM-E1-AU
, PWFY-EP100VM-E2-AU>
Only PWFY
PWFY with standard indoor units
Cooling
Heating
Cooling
Heating
Inlet water temperature
R2/WR2 series
10 to 35ºC
10 to 40ºC
10 to 35ºC
10 to 40ºC
Y/HP/WY series
10 to 35ºC
10 to 40ºC
10 to 35ºC
10 to 40ºC
Outdoor temperature
R2 series
-5 to 46ºCDB
-20 to 32ºCWB
-5 to 46ºCDB
-20 to 32ºCWB
Y series
-5 to 46ºCDB
-20 to 15.5ºCWB
-5 to 46ºCDB
-20 to 15.5ºCWB
HP series
-5 to 43ºCDB
-25 to 15.5ºCWB
-5 to 43ºCDB
-25 to 15.5ºCWB
Circulating water
temperature
WR2 series
10 to 45ºC
10 to 45ºC
10 to 45ºC
10 to 45ºC
WYseries
10 to 45ºC
10 to 45ºC
10 to 45ºC
10 to 45ºC
Only standard indoor units
Cooling
Heating
Outdoor temperature
R2 series
-5 to 46ºCDB
-20 to 15.5ºCWB
Y series
-5 to 52ºCDB
-20 to 15.5ºCWB
HP series
-5 to 43ºCDB
-25 to 15.5ºCWB
Circulating water
temperature
WR2 series
10 to 45ºC
10 to 45ºC
WYseries
10 to 45ºC
10 to 45ºC
General Equipment Descriptions