- 60 -
(4) Transmission cable specifications
(4)-1 Transmission cables
PWFY-P100VM-E-BU
(5) Connecting electrical connections
*1 Connected with simple remote controller. CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CVV, MVV : PVC insulated PVC sheathed control cable
CPEVS
: PE insulated PVC jacketed shielded communication cable
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
MA Remote controller cables
Sheathed 2-core cable (shielded)
CVVS
0.3 ~ 1.25 mm
2
(0.75 ~ 1.25 mm
2
)*1
Max.length: 200 m
External input
Sheathed multi-core cable (shielded)
CVVS or MVVS
0.3 ~ 0.5 mm
2
Max.length: 100 m
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3 ~ 1.25 mm
2
Rated voltage: L1-N: 220 ~ 240 V
Rated load: 0.6 A
Type of cable
Cable diameter
Remarks
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
-
MA Remote controller cables
Sheathed 2-core cable
CVV (unshielded)
0.3 ~ 1.25 mm
2
(0.75 ~ 1.25 mm
2
)*1
Max.length: 200 m
External input
Sheathed multi-core cable
CVV or MVV (unshielded)
0.3 ~ 0.5 mm
2
Max.length: 100 m
External output
Sheathed multi-core cable (unshielded)
CVV or MVV
0.3 ~ 1.25 mm
2
Rated voltage: L1-N: 220 ~ 240 V
Rated load: 0.6 A
PWFY-EP100VM-E1/E2-AU
(A) Screws
(B) Front panel
(C) Control box
(A)
(C)
(B)
Verify that the model name on the operating instructions on the cover of the control box is the same as the model name
on the nameplate.
Step 1
Remove the screws holding the terminal box cover in place.
[Fig. V.1.(5).1]
•PWFY unit •Solenoid valve kit
(A)
(C)
(A)
(B)
(A)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover. Pinching the wiring may cut it.
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.