11. M-NET CONTROL
Hyper Heating Inverter Y-Series
11-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
2. Address should be set to Indoor units and central controller.
3. For a system having more than 32 indoor unit, confirm the need of Booster at
11-3. "System configuration restrictions".
4. When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their
address.
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*SC can be connected to TB3 side or TB7 side;
Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
Up to three System controllers can be connected to TB3 side.
01
02
03
04
05
TB15
TB5
TB5
TB5
TB5
TB5
MA R/C
TB15
TB15
TB15
TB15
SRU
Wireless R/C
*1
*1
Group 2
Group 1
Group 3
Group 4
TB3
TB3
TB3
201
53
52
51
OC
OS1
OS2
SC
TB3
TB3
52
51
OC
OS1
TB3
51
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
<Three outdoor units>
<Two outdoor units>
<One outdoor unit>
PUHY
PUHY
PUHY