13. OUTDOOR INSTALLATION
Hyper Heating Inverter Y-Series
<PUHY-HP144, 192, 240TSNU/YSNU>
To Indoor unit
twinning pipe
200mm [7-7/8 in.]
max.
Outdoor unit 2
Outdoor unit 1
The length of the straight pipe must be 500mm[19-11/16 in.] or longer.
If not, it may cause improper operation.
CAUTION
See the following drawing for connecting the pipes between the outdoor units.
<In case of 2units combination>
13-3-7. Twinning on the outdoor unit side
On-site piping
On-site piping
Twining Kit
The pipe section before the pipe
must have at least 500 mm
(19-1
1/16 in) of straight section.