11. M-NET CONTROL
Hyper Heating Inverter Y-Series
11-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
2. Address should be set to Indoor units, Lossnay and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to
11-3. "System configuration restrictions".
4. When a PAR-CT01MAU or PAR-40MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
Indoor unit
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
*1
*1
01
02
03
30
TB15
TB5
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA-G
TB5
TB15
TB15
TB3
TB15
MA R/C
(Main)
(Sub)
MA R/C
TB15
Indoor unit
MA R/C
SRU
Wireless R/C
*1
*1
41
44
45
TB15
TB5
TB5
TB5
TB15
Group 2
Group 1
Group 21
Group 31
Group 33
Group 34
TB3
TB3
TB7
TB7
TB7
TB7
TB7
TB7
TB3
53
52
51
OC
OS1
OS2
PUHY
PUHY
PUHY
TB3
TB3
92
91
OC
OS1
TB3
97
OC
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
ON
DipSW5-1
202
*2 *4
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A-A, 24VDC should be used with the PAC-SC51KUA.
For AE-200A, AE-50A, and EW-50A the power supply unit PAC-SC51KUA is unused.
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
AE-200A, AE-50A, EW-50A, and BAC-HD150 are for exclusive use as a "main" system controller and cannot be used as a “sub” system
*4 The power supply unit is not necessary for AE-200A, AE-50A, EW-50A, BAC-HD150, and LM-AP.
controller. Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
000 or 201
PSU
Power supply unit (PSU)
(PAC-SC51KUA)
SC*3
SC
*3
203
SC
*3
ME R/C
142
42
43
TB5
Lossnay
Interlocked with
M-NET address 42
TB5
Group 32
NOTE: