10. ELECTRICAL WORK
Hyper Heating Inverter Y-Series
10-2. Power supply for Outdoor unit
10-2-1. Electrical characteristics of Outdoor unit at cooling mode
MOP is used to select the fuse, switch, or breaker for current leakage.
Symbols: MCA: Minimum Circuit Ampacity
PUHY-HP-T(S)NU
SC: Starting Current
MOP: Maximum Overcurrent Protection
Model name
Combination
Outdoor Units
Compressor
Fan
Hz
Volts
Voltage
range
MCA (A) MOP (A) Output
(kW)
SC (A)
Output (kW)
PUHY-HP72TNU-A
-
60Hz 208/230V 188 to 253V
38/35
60/50
3.8
15
0.46+0.46
PUHY-HP96TNU-A
-
43/40
70/60
4.5
15
0.46+0.46
PUHY-HP120TNU-A
-
47/43
70/60
6.5
15
0.46+0.46
PUHY-HP144TSNU-A
PUHY-HP72TNU-A
38/35
60/50
3.8
15
0.46+0.46
PUHY-HP72TNU-A
38/35
60/50
3.8
15
0.46+0.46
PUHY-HP192TSNU-A
PUHY-HP96TNU-A
43/40
70/60
4.5
15
0.46+0.46
PUHY-HP96TNU-A
43/40
70/60
4.5
15
0.46+0.46
PUHY-HP240TSNU-A
PUHY-HP120TNU-A
47/43
70/60
6.5
15
0.46+0.46
PUHY-HP120TNU-A
47/43
70/60
6.5
15
0.46+0.46
PUHY-HP-Y(S)NU
Model name
Combination
Outdoor Units
Compressor
Fan
Hz
Volts
Voltage
range
MCA (A) MOP (A) Output
(kW)
SC (A)
Output (kW)
PUHY-HP72YNU-A
-
60Hz
460V
414 to 506V
17
25
3.8
7
0.46+0.46
PUHY-HP96YNU-A
-
20
30
4.5
7
0.46+0.46
PUHY-HP120YNU-A
-
21
35
6.5
7
0.46+0.46
PUHY-HP144YSNU-A
PUHY-HP72YNU-A
17
25
3.8
7
0.46+0.46
PUHY-HP72YNU-A
17
25
3.8
7
0.46+0.46
PUHY-HP192YSNU-A
PUHY-HP96YNU-A
20
30
4.5
7
0.46+0.46
PUHY-HP96YNU-A
20
30
4.5
7
0.46+0.46
PUHY-HP240YSNU-A
PUHY-HP120YNU-A
21
35
6.5
7
0.46+0.46
PUHY-HP120YNU-A
21
35
6.5
7
0.46+0.46