15
2. EXTERNAL DIMENSIONS
Hyper Heating Inverter Y-Series
Unit: mm (in.)
PUHY-HP72, 96, 120TNU-A
●
In case of collective installation
1 When multiple units are installed adjacent to each other
, secure enough space to allow
for air circulation and walkway between groups of units as shown
in the figures below
.
2
At least two sides must be left open.
3
As with the single installation, add the height that exceeds the he
ight limit<h>
to the figures that are marked with an asterisk.
4 If there is a wall at both the front and the rear of the unit, install
up to six units
consecutively in the side direction and provide a space of 1000mm(3
9-3/8) or more as inlet space/
passage space for each six units.
1
Take into consideration the surface strength, water drainage route,
piping route, and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
2 Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
3
The protrusion length of the anchor bolt must not exceed 30mm(1-3/16).(Fig.A)
4 Use four fixing plates as shown in the right figure <field supply required>
when using M12 hole-in anchor bolts <field supply required>.(Fig.B)
5
To prevent small animals and water and snow from entering the unit and damaging its parts,
close the gap around the edges of through holes for pipes and wires with
filler plates <field supply required>.
6 When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
7 Refer to the Installation Manual when installing units on an installation base.
2. Foundation work
1. Required space around the unit
●In case of single installation
<W
all height limit> Front : Up to the unit height
Back
: Up to the unit height
Side
: Up to the unit height
Front
Unit height
H
Unit height
H
h
h
<Side view>
2 When the height of the walls on the front, back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
<T
op view>
<Unit:mm(in)>
<T
op view>
1 Secure enough space around the unit as shown in the figure below
.
· With a space of at least
450mm(17-3/4) to the wall
on the back of the unit
· With a space of at least
300mm(1
1-13/16) to the wall
on the back of the unit
Front
Front
30 min.*
(1-3/16)
30 min.*
(1-3/16)
450 min.*
(17-3/4)
450 min.*
(17-3/4)
300 min.*
(11-13/16)
450 min.*
(17-3/4)
450 min.*
(17-3/4)
450 min.*
(17-3/4)
M10 anchor bolt
<field supply required>
Fixing plate
<field supply required>
30mm max.
(1-3/16)
<T o be left open>
Front
W
all <H>
<T
o be left open>
Front
<Unit:mm(in)>
W
all <H>
<T o be left open>
<T o be left open>
<T o be left open>
Front
W
all <H>
W
all <H>
Wall <H>
Wall <H>
Front
Front
<T
o be left open>
W
all <H>
Front
W
all <H>
<T o be left open>
<T o be left open>
Front
Front
Front
W
all <H>
W
all <H>
Front
<T o be left open>
<T
o be left open>
450 min.*
(17-3/4)
450 min.
(17-3/4)
30 min.
(1-3/16)
450 min.
(17-3/4)
450 min.*
(17-3/4)
450 min.
(17-3/4)
300 min.*
(1
1-13/16)
450 min.*
(17-3/4)
300 min.*
(11-13/16)
450 min.*
(17-3/4)
900 min.
450 min.*
(17-3/4)
900 min.
450 min.*
(17-3/4)
30 min.*
(1-3/16)
(35-7/16)
(35-7/16)
1000 min.
*
(39-3/8)
450 min.
(17-3/4)
450 min.
(17-3/4)
Fig.A
Fig.B
450 min.*
(17-3/4)