background image

8

D

F

E

I

NL

P

GR

RU

TR

CZ

SV

HG

PO

Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-
ing particles, oils, moisture, or any other contaminant.

- Contaminants on the inside of the refrigerant piping may cause the refriger-

ant residual oil to deteriorate.

Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing. (Store elbows and
other joints in a plastic bag.)

- If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and

compressor trouble may result.

Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator
oil to coat flares and flange connections.

- The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.

Use liquid refrigerant to fill the system.

- If gas refrigerant is used to seal the system, the composition of the refriger-

ant in the cylinder will change and performance may drop.

Do not use a refrigerant other than R410A.

- If another refrigerant is used, the chlorine in the refrigerant and the refriger-

ant oil in the existing piping may cause the refrigerator oil to deteriorate.

Use a vacuum pump with a reverse flow check valve.

- The vacuum pump oil may flow back into the refrigerant cycle and cause the

refrigerator oil to deteriorate.

Do not use the following tools that are used with conventional refriger-
ants.
(Gauge manifold, charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, vacuum gauge, refrigerant recovery equipment)

- If the conventional refrigerant and refrigerator oil are mixed in the R410A,

the refrigerant may deteriorated.

- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-

tional refrigerants will not react to it.

Do not use a charging cylinder.

- Using a charging cylinder may cause the refrigerant to deteriorate.

Be especially careful when managing the tools.

- If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deterio-

rate.

1.3. Before getting installed

 Caution:

Do not install the unit where combustible gas may leak.

- If the gas leaks and accumulates around the unit, an explosion may result.

Do not use the air conditioner where food, pets, plants, precision instru-
ments, or artwork are kept.

- The quality of the food, etc. may deteriorate.

Do not use the air conditioner in special environments.

- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of

the air conditioner or damage its parts.

When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.

- The inverter equipment, private power generator, high-frequency medical

equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air condi-
tioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.

Do not install the unit on a structure that may cause leakage.

- When the room humidity exceeds 80 % or when the drain pipe is clogged,

condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.

The indoor models should be installed more than 2.5 m [9 ft] from floor.

1.4. Before installation (moved) -

electrical work

 Caution:

Ground the unit.

- Do not connect the ground wire to gas or water pipes, lightning rods, or

telephone ground lines. Improper grounding may result in electric shock.

Install the power cable so that tension is not applied to the cable.

- Tension may cause the cable to break and generate heat and cause a fire.

Install a leak circuit breaker, as required.

- If a leak circuit breaker is not installed, electric shock may result.

Use power line cables of sufficient current carrying capacity and rating.

- Cables that are too small may leak, generate heat, and cause a fire.

Use only a circuit breaker and fuse of the specified capacity.

- A fuse or circuit breaker of a larger capacity or a steel or copper wire may

result in a general unit failure or fire.

Do not wash the air conditioner units.

- Washing them may cause an electric shock.

Be careful that the installation base is not damaged by long use.

- If the damage is left uncorrected, the unit may fall and cause personal injury

or property damage.

Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.

- Improper drain piping may cause water leakage and damage to furniture

and other possessions.

Be very careful about product transportation.

- One person should not carry the product if it weighs more than 20 kg [45

LBS].

- Some products use polypropylene bands for packaging. Do not use any

polypropylene bands for a means of transportation. It is dangerous.

- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on

the unit base. Also support the outdoor unit at four points so that it cannot
slip sideways.

Safely dispose of the packing materials.

- Packing materials, such as nails and other metal or wooden parts, may cause

stabs or other injuries.

- Tear apart and throw away plastic packaging bags so that children will not

play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.

1.5. Before starting the test run

 Caution:

Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can

result in severe damage to internal parts. Keep the power switch turned on
during the operational season.

Do not touch the switches with wet fingers.

- Touching a switch with wet fingers can cause electric shock.

Do not touch the refrigerant pipes during and immediately after opera-
tion.

- During and immediately after operation, the refrigerant pipes may be hot and

may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.

Do not operate the air conditioner with the panels and guards removed.

- Rotating, hot, or high-voltage parts can cause injuries.

Do not turn off the power immediately after stopping operation.

- Always wait at least five minutes before turning off the power. Otherwise,

water leakage and trouble may occur.

2. Indoor unit accessories

The unit is provided with the following accessories:

Part No.

Accessories

CFM

CFMR

1

Installation manual

1

1

2

Operation manual

1

1

3

Washer (for hanging)

8

8

4

Connector assy (for external static pressure switch)
[Red: middle pressure]

1

1

5

Connector assy (for external static pressure switch)
[Blue: low pressure]

1

1

6

Pipe cover (for refrigerant piping joint)
120 mm [3/4 in.] Small diameter

1

2

7

Pipe cover (for refrigerant piping joint)
120 mm [3/4 in.] Large diameter

1

2

Part No.

Accessories

CFM

CFMR

8

Tie (short)

2

2

9

Tie (long)

5

9

10

Drain hose

1

1

11

Pipe cover (for drain hose) 60 mm [3/8 in.]

1

1

12

Pipe cover (for drain hose) 25 mm [1 in.]

1

1

13

Washer (for power source wiring)

1

1

14

Reducer 19.05 - 22.2 mm [3/4-7/8 in.] (for gas pipe)

1

15

Reducer 9.52 - 12.7 mm [3/8-1/2 in.] (for liquid pipe)

1

Summary of Contents for City Multi PEFY-AF1200CFM

Page 1: ... correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte English Français ...

Page 2: ...8 B Liquid refrigerant piping brazing connection of main coil ø9 52 3 8 C Gas refrigerant piping brazing connection of reheat coil ø22 2 7 8 D Liquid refrigerant piping brazing connection of reheat coil ø9 52 3 8 E Drain pipe O D ø32 1 1 4 primary draining F Drain pipe O D ø32 1 1 4 secondary draining G Drain pipe O D ø32 1 1 4 6 6 2 Fig 6 2 1 Unit mm in 395 15 9 16 96 3 13 16 604 23 13 16 524 20 ...

Page 3: ... AF1200CFMR C B D A E E F E F Insulation pipe small accessory G Caution Pull out the insulation on the refrigerant piping at the site braze the piping and replace the insulation in its original position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant pi...

Page 4: ...tion must be positioned up Fig 7 2 3 A Indoor unit B Insulation short accessory C Tie short accessory D Attaching the band E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC field supplied H Insulation field supplied I Max 145 5 mm 5 23 32 7 32 in D E H G I F B C 5 7 32 A 25 1 Unit mm in Unit mm in SWE Correct piping Wrong piping A Insulation 9 mm 3 8 in or more B Decli...

Page 5: ... A Non polarized B TB15 C Remote Controller D TB5 Fig 9 2 3 Fig 9 2 4 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L1 L2 G C D A S M2 M1 B 1 2 L1 L2 G DC24 30V A B 1 2 C E D C B A F E 9 2 Fig 9 1 2 PEFY AF1200CFM Fig 9 1 3 PEFY AF1200CFMR B A B A C T S HMU 3 208 230V Y S HMU 3 460V L1 L2 L3 208 230V L1 L2 Ground Ground D A Switch Breakers for wiring and current leak B Breakers for current leak C Outdoor uni...

Page 6: ...Shield wire D The ground wire from two cables are connected together to the S terminal Dead end connection E Insulation tape To keep the ground wire of the shielded cable from coming in contact with the transmission terminal Indoor controller board 9 3 Fig 9 3 3 Fig 9 3 4 Fig 9 5 1 Fig 9 3 5 9 5 A Terminal block box B Knockout hole C Remove A Screw 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B C A B A A B ...

Page 7: ... properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditio...

Page 8: ...ng rods or telephone ground lines Improper grounding may result in electric shock Install the power cable so that tension is not applied to the cable Tension may cause the cable to break and generate heat and cause a fire Install a leak circuit breaker as required If a leak circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and ...

Page 9: ...leaks Be sure to check the position s s s s s Use a level to check that the surface indicated by A A A A A is at level Ensure that the hanging bolt nuts are tightened to fix the hanging bolts s s s s s To ensure that drain is discharged be sure to hang the unit at level using a level Caution Install the unit in horizontal position If the side with the drain port is in stalled higher it may cause w...

Page 10: ...iginal position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant piping M Ensure that there are no gaps between the insulation and the body N Tie long accessory O Ensure that there is no gap here Joint should face up For PEFY AF1200CFMR Use the supplied ...

Page 11: ...unit pipe This metal brace should be 50 cm 19 11 16 in away from the indoor unit s flare connection Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant specified on the unit Mixing of a different refrigerant air etc may cause the refrigerant cycle to mal function and result in severe damage Caution Use refrigerant piping made of C1220 Cu DHP pho...

Page 12: ...g in direct contact with the power cable outside the unit 3 Ensure that there is no slack on all wire connections 4 Some cables power remote controller transmission cables above the ceiling may be bitten by rodent Use as many metal pipes as possible to protect the cables 5 Never connect the power cable to leads for the transmission cables Otherwise the cables would be broken 6 Be sure to connect c...

Page 13: ...n polarized 2 wire Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire Connect the remote controller s transmission cable within 10 m 32 ft using a 0 75 mm2 AWG18 core cable If the distance is more than 10 m 32 ft use a 1 25 mm2 AWG16 junction cable Fig 9 2 1 P 5 MA Remote controller Fig 9 2 2 P 5 M NET Remote controller A Terminal block for indoor transmissi...

Page 14: ...ntrol board reheat unit that equals the address of the right control board main unit plus 1 Fig 9 5 2 P 6 A Indoor controller board main B Indoor controller board reheat The rotary switches are all set to 0 when shipped from the factory These switches can be used to set unit addresses and branch numbers at will The determination of indoor unit addresses varies with the system at site Set them refe...

Page 15: ... un incendie ou de la fumée pourrait en résulter Mettez fermement en place le couvercle des bornes de l appareil extérieur panneau Si le couvercle des bornes panneau n est pas mis en place correctement il se peut que de la poussière ou de l eau s infiltre dans l appareil extérieur et par conséquent il y aura un risque d incendie ou d électrocution Lors du déplacement et de l installation du climat...

Page 16: ...ut que le climatiseur ait un effet nuisible sur ce genre d équipements en faisant du bruit qui gênerait les traitements médicaux ou l envoi d images N installez pas l appareil sur une structure qui pourrait causer des fui tes Lorsque l humidité de la pièce dépasse 80 ou lorsque le tuyau d écoule ment est bouché il se peut que des gouttes d eau tombent de l appareil intérieur Veillez à fournir une ...

Page 17: ... une distribution homogène de l air dans la pièce Ne pas installer l appareil dans un endroit sujet à des éclaboussures de graisse ou à de grandes quantités de vapeur Ne pas installer l appareil dans un endroit avec arrivée de gaz combustible entrepôt de gaz ou sujet à des fuites de gaz Ne pas installer l appareil dans un endroit contenant des équipements qui pro duisent des ondes de haute fréquen...

Page 18: ...portez vous au manuel de l appareil extérieur Brasez les connexions des tuyaux Précaution Installer les tuyaux de réfrigérant pour l appareil intérieur conformément aux instructions suivantes 7 Raccordement des tuyaux de réfrigérant et d écoulement 7 1 Mise en place des tuyaux de réfrigérant Les travaux de raccordement des tuyaux doivent être faits conformément aux ins tructions des manuels d inst...

Page 19: ...sières saletés de particules de rasage d huile d hu midité ou de n importe quel autre contaminant dangereux N utilisez jamais les tuyaux de réfrigérant déjà en place La quantité importante de chlore contenue dans les réfrigérants tradition nels et l huile réfrigérante des tuyaux actuels provoquera la détérioration du nouveau réfrigérant Entreposez à l intérieur la tuyauterie à utiliser et gardez s...

Page 20: ...se en place des câbles de transmission Types de câbles de transmission Concevoir le câblage conformément aux indications reprises dans le tableau suivant Table1 Diamètre des câbles Plus de 1 25 mm2 AWG16 8 Raccords des conduites Lors du raccordement des conduits insérer une protection en canevas entre le corps principal et le tuyau Utiliser des composants pour conduits ininflammables Installer une...

Page 21: ...urce d alimentation 208V 230V Câble principal Commutateur A Épaisseur minimale du câble mm2 AWG Embranchement Capacité Fusible Disjoncteur pour Terre Modèle Combinaison d appareil Disjoncteur pour fuite de courant câblage NFB A Appareil extérieur PUHY P72THMU A BS PUHY P96THMU A BS PUHY P120THMU A BS 30 A 30 mA ou 100 mA 0 1 sec ou moins 40 A 30 mA ou 100 mA 0 1 sec ou moins 50 A 100 mA 0 1 sec ou...

Page 22: ...borne de transmission 5 Lorsque le câblage est terminé vérifier qu il n y a pas de jeu dans les con nexions et fixer le couvercle au bloc de raccordement en procédant dans l or dre inverse au démontage Remarques Faire attention à ne pas coincer les câbles ou les fils en rattachant le couvercle de la boîte de commandes sinon ceux ci risquent de se dé brancher Lors de la fixation de la boîte de comm...

Page 23: ...GB E F I NL E P GR RU TR ...

Page 24: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: