background image

7

D

F

E

I

NL

P

GR

RU

CZ

SV

HG

PO

Contents

1. Safety precautions

1.1. Before installation and electric work

s

Before installing the unit, make sure you read all the “Safety
precautions”.

s

The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.

Symbols used in the text

 Warning:

Describes precautions that should be observed to prevent danger of injury
or death to the user.

 Caution:

Describes precautions that should be observed to prevent damage to the
unit.

Symbols used in the illustrations

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Indicates that caution should be taken with rotating parts. (This symbol is

displayed on the main unit label.) <Color: Yellow>

: Beware of electric shock. (This symbol is displayed on the main unit label.)

<Color: Yellow>

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

Ask the dealer or an authorized technician to install the air conditioner.

- Improper installation by the user may result in water leakage, electric shock,

or fire.

Install the air unit at a place that can withstand its weight.

- Inadequate strength may cause the unit to fall down, resulting in injuries.

Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.

- Inadequate connection and fastening may generate heat and cause a fire.

Prepare for typhoons and other strong winds and earthquakes and in-
stall the unit at the specified place.

- Improper installation may cause the unit to topple and result in injury.

Always use an air cleaner, humidifier, electric heater, and other accesso-
ries specified by Mitsubishi Electric.

- Ask an authorized technician to install the accessories. Improper installation

by the user may result in water leakage, electric shock, or fire.

Never repair the unit. If the air conditioner must be repaired, consult the
dealer.

- If the unit is repaired improperly, water leakage, electric shock, or fire may

result.

Do not touch the heat exchanger fins.

- Improper handling may result in injury.

When handling this product, always wear protective equipment.
EG: Gloves, full arm protection namely boiler suit, and safety glasses.

- Improper handling may result in injury.

If refrigerant gas leaks during installation work, ventilate the room.

- If the refrigerant gas comes into contact with a flame, poisonous gases will

be released.

Install the air conditioner according to this Installation Manual.

- If the unit is installed improperly, water leakage, electric shock, or fire may

result.

Have all electric work done by a licensed electrician according to “Elec-
tric Facility Engineering Standard” and “Interior Wire Regulations”and
the instructions given in this manual and always use a special circuit.

- If the power source capacity is inadequate or electric work is performed im-

properly, electric shock and fire may result.

Keep the electric parts away from water (washing water etc.).

- It might result in electric shock, catching fire or smoke.

Securely install the outdoor unit terminal cover (panel).

- If the terminal cover (panel) is not installed properly, dust or water may enter

the outdoor unit and fire or electric shock may result.

When installing and moving the air conditioner to another site, do not
charge it with a refrigerant different from the refrigerant specified on the
unit.

- If a different refrigerant or air is mixed with the original refrigerant, the refrig-

erant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration from exceeding the safety limit
even if the refrigerant should leak.

- Consult the dealer regarding the appropriate measures to prevent the safety

limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.

When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.

- If the air conditioner is installed improperly, water leakage, electric shock, or

fire may result.

After completing installation work, make sure that refrigerant gas is not
leaking.

- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or

other heat source, it may generate noxious gases.

Do not reconstruct or change the settings of the protection devices.

- If the pressure switch, thermal switch, or other protection device is shorted

and operated forcibly, or parts other than those specified by Mitsubishi Elec-
tric are used, fire or explosion may result.

To dispose of this product, consult your dealer.

Do not use a leak detection additive.

When installing or relocating the unit, check that no substance other than
the specific refrigerant (R410A) is present in the refrigerant circuit.

- Infiltration of other substance may cause the pressure to rise abnormally

high and poses a risk of pipe bursting and explosion.

1.2. Precautions for devices that use R410A

refrigerant

 Caution:

Do not use the existing refrigerant piping.

- The old refrigerant and refrigerator oil in the existing piping contains a large

amount of chlorine which may cause the refrigerator oil of the new unit to
deteriorate.

1. Safety precautions ...................................................................................... 7

1.1. Before installation and electric work .......................................... 7
1.2. Precautions for devices that use R410A refrigerant .................. 7
1.3. Before getting installed .............................................................. 8
1.4. Before installation (moved) - electrical work .............................. 8
1.5. Before starting the test run ........................................................ 8

2. Indoor unit accessories ............................................................................... 8
3. Selecting an installation site ....................................................................... 9

3.1. Install the indoor unit on a ceiling strong enough to sustain

its weight ................................................................................... 9

3.2. Securing installation and service space .................................... 9
3.3. Connecting indoor units with outdoor units ............................... 9

4. Fixing hanging bolts .................................................................................... 9

4.1 Fixing hanging bolts .................................................................. 9

5. Installing the unit ......................................................................................... 9

5.1. Hanging the unit body ............................................................... 9
5.2. Confirming the unit’s position and fixing hanging bolts ............. 9

6. Refrigerant pipe and drain pipe specifications .......................................... 10

6.1. Refrigerant pipe and drain pipe specifications ........................ 10
6.2. Refrigerant pipe, drain pipe ..................................................... 10

7. Connecting refrigerant pipes and drain pipes ........................................... 10

7.1. Refrigerant piping work ........................................................... 10
7.2. Drain piping work ..................................................................... 11
7.3. Confirming drain discharge ..................................................... 11

8. Duct work .................................................................................................. 11
9. Electrical wiring ......................................................................................... 12

9.1. Power supply wiring ................................................................. 12
9.2. Connecting remote controller, indoor and outdoor

transmission cables ................................................................. 13

9.3. Connecting electrical connections ........................................... 13
9.4. External I/O specifications ....................................................... 14
9.5. Selecting the external static pressure ..................................... 14
9.6. Setting addresses .................................................................... 14
9.7. Setting a dew point temperature ............................................. 14

Summary of Contents for City Multi PEFY-AF1200CFM

Page 1: ... correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte English Français ...

Page 2: ...8 B Liquid refrigerant piping brazing connection of main coil ø9 52 3 8 C Gas refrigerant piping brazing connection of reheat coil ø22 2 7 8 D Liquid refrigerant piping brazing connection of reheat coil ø9 52 3 8 E Drain pipe O D ø32 1 1 4 primary draining F Drain pipe O D ø32 1 1 4 secondary draining G Drain pipe O D ø32 1 1 4 6 6 2 Fig 6 2 1 Unit mm in 395 15 9 16 96 3 13 16 604 23 13 16 524 20 ...

Page 3: ... AF1200CFMR C B D A E E F E F Insulation pipe small accessory G Caution Pull out the insulation on the refrigerant piping at the site braze the piping and replace the insulation in its original position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant pi...

Page 4: ...tion must be positioned up Fig 7 2 3 A Indoor unit B Insulation short accessory C Tie short accessory D Attaching the band E Insertion margin F Drain hose accessory G Drain pipe O D ø32 mm 1 1 4 in PVC field supplied H Insulation field supplied I Max 145 5 mm 5 23 32 7 32 in D E H G I F B C 5 7 32 A 25 1 Unit mm in Unit mm in SWE Correct piping Wrong piping A Insulation 9 mm 3 8 in or more B Decli...

Page 5: ... A Non polarized B TB15 C Remote Controller D TB5 Fig 9 2 3 Fig 9 2 4 2 S M2 M1 A B D 1 DC10 13V A B 1 2 L1 L2 G C D A S M2 M1 B 1 2 L1 L2 G DC24 30V A B 1 2 C E D C B A F E 9 2 Fig 9 1 2 PEFY AF1200CFM Fig 9 1 3 PEFY AF1200CFMR B A B A C T S HMU 3 208 230V Y S HMU 3 460V L1 L2 L3 208 230V L1 L2 Ground Ground D A Switch Breakers for wiring and current leak B Breakers for current leak C Outdoor uni...

Page 6: ...Shield wire D The ground wire from two cables are connected together to the S terminal Dead end connection E Insulation tape To keep the ground wire of the shielded cable from coming in contact with the transmission terminal Indoor controller board 9 3 Fig 9 3 3 Fig 9 3 4 Fig 9 5 1 Fig 9 3 5 9 5 A Terminal block box B Knockout hole C Remove A Screw 2pcs B Cover Fig 9 3 1 Fig 9 3 2 A B C A B A A B ...

Page 7: ... properly dust or water may enter the outdoor unit and fire or electric shock may result When installing and moving the air conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrig erant cycle may malfunction and the unit may be damaged If the air conditio...

Page 8: ...ng rods or telephone ground lines Improper grounding may result in electric shock Install the power cable so that tension is not applied to the cable Tension may cause the cable to break and generate heat and cause a fire Install a leak circuit breaker as required If a leak circuit breaker is not installed electric shock may result Use power line cables of sufficient current carrying capacity and ...

Page 9: ...leaks Be sure to check the position s s s s s Use a level to check that the surface indicated by A A A A A is at level Ensure that the hanging bolt nuts are tightened to fix the hanging bolts s s s s s To ensure that drain is discharged be sure to hang the unit at level using a level Caution Install the unit in horizontal position If the side with the drain port is in stalled higher it may cause w...

Page 10: ...iginal position Take care to ensure that condensation does not form on exposed copper piping H Liquid refrigerant piping I Gas refrigerant piping J Main body K Insulation pipe large accessory L Site refrigerant piping M Ensure that there are no gaps between the insulation and the body N Tie long accessory O Ensure that there is no gap here Joint should face up For PEFY AF1200CFMR Use the supplied ...

Page 11: ...unit pipe This metal brace should be 50 cm 19 11 16 in away from the indoor unit s flare connection Warning When installing and moving the unit do not charge it with refrigerant other than the refrigerant specified on the unit Mixing of a different refrigerant air etc may cause the refrigerant cycle to mal function and result in severe damage Caution Use refrigerant piping made of C1220 Cu DHP pho...

Page 12: ...g in direct contact with the power cable outside the unit 3 Ensure that there is no slack on all wire connections 4 Some cables power remote controller transmission cables above the ceiling may be bitten by rodent Use as many metal pipes as possible to protect the cables 5 Never connect the power cable to leads for the transmission cables Otherwise the cables would be broken 6 Be sure to connect c...

Page 13: ...n polarized 2 wire Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire Connect the remote controller s transmission cable within 10 m 32 ft using a 0 75 mm2 AWG18 core cable If the distance is more than 10 m 32 ft use a 1 25 mm2 AWG16 junction cable Fig 9 2 1 P 5 MA Remote controller Fig 9 2 2 P 5 M NET Remote controller A Terminal block for indoor transmissi...

Page 14: ...ntrol board reheat unit that equals the address of the right control board main unit plus 1 Fig 9 5 2 P 6 A Indoor controller board main B Indoor controller board reheat The rotary switches are all set to 0 when shipped from the factory These switches can be used to set unit addresses and branch numbers at will The determination of indoor unit addresses varies with the system at site Set them refe...

Page 15: ... un incendie ou de la fumée pourrait en résulter Mettez fermement en place le couvercle des bornes de l appareil extérieur panneau Si le couvercle des bornes panneau n est pas mis en place correctement il se peut que de la poussière ou de l eau s infiltre dans l appareil extérieur et par conséquent il y aura un risque d incendie ou d électrocution Lors du déplacement et de l installation du climat...

Page 16: ...ut que le climatiseur ait un effet nuisible sur ce genre d équipements en faisant du bruit qui gênerait les traitements médicaux ou l envoi d images N installez pas l appareil sur une structure qui pourrait causer des fui tes Lorsque l humidité de la pièce dépasse 80 ou lorsque le tuyau d écoule ment est bouché il se peut que des gouttes d eau tombent de l appareil intérieur Veillez à fournir une ...

Page 17: ... une distribution homogène de l air dans la pièce Ne pas installer l appareil dans un endroit sujet à des éclaboussures de graisse ou à de grandes quantités de vapeur Ne pas installer l appareil dans un endroit avec arrivée de gaz combustible entrepôt de gaz ou sujet à des fuites de gaz Ne pas installer l appareil dans un endroit contenant des équipements qui pro duisent des ondes de haute fréquen...

Page 18: ...portez vous au manuel de l appareil extérieur Brasez les connexions des tuyaux Précaution Installer les tuyaux de réfrigérant pour l appareil intérieur conformément aux instructions suivantes 7 Raccordement des tuyaux de réfrigérant et d écoulement 7 1 Mise en place des tuyaux de réfrigérant Les travaux de raccordement des tuyaux doivent être faits conformément aux ins tructions des manuels d inst...

Page 19: ...sières saletés de particules de rasage d huile d hu midité ou de n importe quel autre contaminant dangereux N utilisez jamais les tuyaux de réfrigérant déjà en place La quantité importante de chlore contenue dans les réfrigérants tradition nels et l huile réfrigérante des tuyaux actuels provoquera la détérioration du nouveau réfrigérant Entreposez à l intérieur la tuyauterie à utiliser et gardez s...

Page 20: ...se en place des câbles de transmission Types de câbles de transmission Concevoir le câblage conformément aux indications reprises dans le tableau suivant Table1 Diamètre des câbles Plus de 1 25 mm2 AWG16 8 Raccords des conduites Lors du raccordement des conduits insérer une protection en canevas entre le corps principal et le tuyau Utiliser des composants pour conduits ininflammables Installer une...

Page 21: ...urce d alimentation 208V 230V Câble principal Commutateur A Épaisseur minimale du câble mm2 AWG Embranchement Capacité Fusible Disjoncteur pour Terre Modèle Combinaison d appareil Disjoncteur pour fuite de courant câblage NFB A Appareil extérieur PUHY P72THMU A BS PUHY P96THMU A BS PUHY P120THMU A BS 30 A 30 mA ou 100 mA 0 1 sec ou moins 40 A 30 mA ou 100 mA 0 1 sec ou moins 50 A 100 mA 0 1 sec ou...

Page 22: ...borne de transmission 5 Lorsque le câblage est terminé vérifier qu il n y a pas de jeu dans les con nexions et fixer le couvercle au bloc de raccordement en procédant dans l or dre inverse au démontage Remarques Faire attention à ne pas coincer les câbles ou les fils en rattachant le couvercle de la boîte de commandes sinon ceux ci risquent de se dé brancher Lors de la fixation de la boîte de comm...

Page 23: ...GB E F I NL E P GR RU TR ...

Page 24: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commer cial and light industrial environment ...

Reviews: