Detailed Description of the Module
I/O Signals for the Programmable Controller CPU
3 – 8
MITSUBISHI ELECTRIC
Module restart completed (Xn2), Module restart request (Yn2)
●
A restart is necessary to activate the following new settings:
–
Function mode (Un\G21), refer to section 3.5.2
–
Baud rate (Un\G24), refer to section 3.5.4
–
Node-ID (Un\G27), refer to section 3.5.6
–
NMT master setting, refer to section 4.8.5.
All not saved settings will be lost.
●
To restart the module, please set the module restart request (Yn2) signal to ON. The module will
be set to initialization state as indicated by the Un\G25 bit 7 (refer to section 3.5.5). After the
module is restarted, the module restart completed (Xn2) will be set to ON. The module restart
request (Yn2) signal can be reset to OFF. Not setting this signal back to OFF will cause that the
module will be restarted again and again. The restart procedure will take approx. 6 seconds to
complete.
Module in Layer 2 online mode (Xn3), Layer 2 online mode request (Yn3)
●
The Layer 2 online mode request signal (Yn3) must be set to ON to start data exchange with other
network nodes.
●
The module in Layer 2 online mode signal (Xn3) will turn ON if the module can be set to online
mode. The configuration of the module can only be changed while this signal is OFF..
Message transmit trigger completed (Xn4), Message transmit trigger request (Yn4)
●
The transmission trigger of a message in Layer 2 mode which is set in Un\G8400 to Un\G8402
must be started with a message transmit trigger request (Yn4).
●
The message transmit trigger completed signal (Xn4) will turn ON when all the messages have
been written into the transmit buffer. Please refer also to section 3.6.4.
Fig. 3-4:
Timing of the signals Xn2 and Yn2
NOTE
In case a configuration buffer memory was changed during online mode, Un\G29 bit 5 is set to ON.
Performed by the ME3CAN1-L
Performed by the sequence program
Module restart request (Yn2)
Module restart completed (Xn2)
Module initialization state (Un\G25 bit 7)
OFF
OFF
ON
ON
OFF
ON
Summary of Contents for CANopen ME3CAN1-L
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV ...
Page 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Page 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Page 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Page 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Page 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Page 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Page 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Page 187: ......