This command can be used to send an emergency message by the PLC to the CANopen
network.
Execution procedure: Send an emergency message
●
Write the command code 000A
H
to Un\G1000.
●
Write the Emergency error code
, Error register and Manufacturer-specific error code that will be
sent as the Emergency Message to Un\G1001 to Un\G1004.
Unused emergency data bytes
have to be
filled with "00
H
".
●
After writing the necessary command parameters, turn ON Y(n+1)7 to execute the command. If
the command execution is finished, X(n+1)7 will be turned ON.
Buffer memory allocation
For Emergency error codes please refer to section 8.2.1.
Address
(Decimal)
Description
Transmit message
Receive message
1000
Command 000A
H
: Send emergency message
앫
000B
H
: Command success
앫
000C
H
: Communication error
앫
000F
H
: Error (Refer to section 5.4)
앫
FFFF
H
: CIF Busy
1001
Emergency error code
���
앫
0000
H
: No Error
앫
0001
H
: EMCY Inhibit time not elapsed
앫
0002
H
: Device is not in CANopen
State
Operational
or
Pre-Operational
1002
앫
Low Byte: Error register (Refer to section 4.6.2 and
앫
High Byte: Byte 0 of Manufacturer-specific error
code (msef ) (Refer to section 4.6.12)
Unused
1003
앫
Low Byte: Byte 1 of msef
앫
High Byte: Byte 2 of msef
Unused
1004
앫
Low Byte: Byte 3 of msef
앫
High Byte: Byte 4 of msef
Unused
1005–1066
Unused
Unused
Tab. 5-9:
Buffer memory allocation when sending an emergency message
Summary of Contents for CANopen ME3CAN1-L
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV ...
Page 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Page 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Page 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Page 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Page 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Page 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Page 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Page 187: ......