Buffer Memory Details: CANopen
Mode
Detailed Description of the Module
MELSEC-L Series – CANopen
Module ME3CAN1-L
3 – 21
Timestamp will be only produced if the module is active NMT Master.
If the ME3CAN1-L is setup as "consumer " this buffer memory addresses will be ignored.
3.5.12
NMT Start all Nodes delay (Un\G70)
During the NMT master startup, the NMT master sends, depending on the configuration, a NMT
Reset
communication all Nodes
and NMT
Start all Nodes
.
The value in Un\G70 sets the minimum time between these two NMT messages, to ensure that a slow
NMT Slave recognizes the NMT
Start all Nodes
message.
The value can be set in ms (default: 500 ms).
The setting range is 0 ms to 65535 ms.
3.5.13
SDO Time out (Un\G71)
In Un\G71 the time out for SDO communication is set.
The value can be set in ms (default: 500 ms).
The setting range is 50 ms to 32767 ms.
3.5.14
NMT Error Clear Node (Un\G400)
Un\G400 specifies the number of the node, whose NMT errors are to be cleared.
To clear the NMT errors of all nodes (Un\G401–Un\G527), write 0000
H
to this buffer memory address.
This is also the default setting.
After writing a value to this Un\G400, please execute the NMT error clear by setting the output Y(n+1)0
to ON (Please refer to section 3.3.2).
55
Time stamp
Minute
Value range: 0 to 59
���
56
Second
Value range: 0 to 59
���
57
Day-of-the-week
Display range: 0 to 6 (0: Sunday to 6: Saturday)
���
The Day of the week will be calculated during the setup of
the clock data automatically.
58
Transmission interval
Set the transmission time interval for the Time stamp Object
in multiples of minutes.
���
Setting range:
0 =
Time stamp transmission disabled
1 to 1440 = 1 min to 1440 Minutes (24 hours)
59
Daily correction
A constant miscount of the clock can be corrected in steps
of 1 sec per day.
Setting range: -60 to +60
NOTE
For the NMT Startup process please refer to section 4.8.5.
NOTE
For SDO please refer to section 4.6.4.
Address
(Decimal)
Name
Description / Value range
Tab. 3-15:
Buffer memory addresses for the time stamp
Summary of Contents for CANopen ME3CAN1-L
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ...IV ...
Page 18: ...Abbreviations and Generic Terms Overview MELSEC L Series CANopen Module ME3CAN1 L 1 4 ...
Page 22: ...System Configuration System Equipment 2 4 MITSUBISHI ELECTRIC ...
Page 162: ...Programming Layer 2 Communication 7 24 MITSUBISHI ELECTRIC Program Fig 7 24 Example Program 1 ...
Page 164: ...Programming Layer 2 Communication 7 26 MITSUBISHI ELECTRIC Fig 7 26 Example Program 3 ...
Page 166: ...Programming Layer 2 Communication 7 28 MITSUBISHI ELECTRIC Fig 7 28 Example Program 5 ...
Page 178: ...Layer 2 Communication Programming MELSEC L Series CANopen Module ME3CAN1 L 7 40 ...
Page 184: ...Troubleshooting Error Code and Error Message Summary 8 6 MITSUBISHI ELECTRIC ...
Page 187: ......