8 FUNCTIONS
8.2 Function Details
87
8
Parameter access error detection function
Detects errors that occur during reading or writing of the parameters of a slave module. The following parameter access errors
are detected.
• Slave module hardware error (Error code: 012CH, 012DH)
• Parameter access target module ID error (Error code: 012EH)
• Parameter value error (Error code: 012FH)
• Parameter access error (Error code: 0130H)
• Slave module status error (Error code: 0131H)
• Same ID used error (Error code: 0190H)
• No ID setting error (Error code: 0191H)
How to check the parameter access error status
The following table lists parameter access error statuses.
*1 If multiple errors occur simultaneously, the latest error is displayed.
How to recover from the parameter access error status
How to recover from the parameter access error status is as follows.
■
How to recover from a slave module hardware error
1.
Eliminate the error cause by taking measures such as noise prevention.
Even when Slave module hardware error is cleared, the following status is maintained.
• ON state of Slave module alarm signal (RX(n+1)0)
• The error code stored in Latest error code storage area (RWrn+16)
*1*2
• The error ID stored in Latest error ID storage area (RWrn+17)
*1*2
• The unset ID (02FFH or 00FFH) stored in Latest error ID simple information (RXn6 to RXnF)
*1
• The alarm information is notified from the bridge module to the device of the CPU module.
*2
*1 If multiple errors occur simultaneously, the latest error is displayed.
*2 This applies only when the CC-Link operation mode is Ver.2.00.
2.
Power off and on the AnyWireASLINK system or turn on and off Error reset request flag (RY(n+D)A).
The following status is resulted:
• Slave module alarm signal (RX(n+1)0) turns off.
• The value in Latest error code storage area (RWrn+16) is cleared.
• The value in Latest error ID storage area (RWrn+17) is cleared.
• The value in Latest error ID simple information (RXn6 to RXnF) is cleared.
• The alarm information that was notified to the device of the CPU module is cleared.
Error
Status when the error occurs
Remote I/O signals
Latest error code storage area
(RWrn+16)
Latest error ID storage area
(RWrn+17) and Latest error ID
simple information (RXn6 to
RXnF)
Slave module hardware error
Slave module alarm signal
(RX(n+1)0) turns on.
The error code is stored.
The error ID is stored.
Parameter access target module ID
error
Parameter value error
Parameter access error
Parameter access error (RX(n+1)2)
turns on.
Slave module status error
Slave module alarm signal
(RX(n+1)0) turns on.
Same ID used error
No ID setting error