5 SWITCH SETTING
5.2 AnyWireASLINK Side
39
5
5.2
AnyWireASLINK Side
Number of transmission points setting switch
Set required number of occupied stations and transmission points of CC-Link when CC-Link operation mode is performed.
All switch positions are set to off when the product is shipped.
• When the CC-Link operation mode is Ver.1.10, the number of occupied stations of CC-Link is automatically
determined by setting the number of transmission points of AnyWireASLINK. The transmission cycle time of
CC-Link side and AnyWireASLINK side can be shortened by setting small number of transmission points of
AnyWireASLINK.
• When the CC-Link operation mode is Ver.2.00, the number of occupied stations of CC-Link is fixed at 4. Set
SW1 and SW2 to off. When SW1 and SW2 are not set to off, the setting is ignored and the number of
occupied stations is set to 4.
CC-Link operation mode
SW1
SW2
Number of occupied
stations of CC-Link
Number of transmission points of
AnyWireASLINK
Input
Output
Ver.1.10
Off
Off
4
256
256
On
Off
3
192
192
Off
On
2
128
128
On
On
1
64
64
Ver.2.00
Off
Off
4
256
256
On
Off
N/A
Off
On
On
On
Summary of Contents for AnyWire NZ2AW1C2AL