4 CONNECTIONS
4.4 Supplying Power to a Bridge Module
■
Description of the condition 1)
• Constants related to the non-isolated slave module (Ihin, Iho)
In the non-isolated slave module, the current required for the internal control circuit and the connected load is supplied with
transmission cables (DP, DN).
Ihin(A)
= Current consumption of the non-isolated input slave module/I/O combined slave module
= Current consumption of the non-isolated input slave module/I/O combined slave Current consumption of
connected load (three-wire sensor)
Number of points
Iho(A)
= Current consumption of the non-isolated output slave module
= Current consumption of the non-isolated output slave Current consumption of connected load
Number of points
• The 24VL and 0VL terminals of a slave module are used to supply the power to the connected load.
• For the current consumption of a non-isolated slave module, refer to the manual for the slave module used.
Non-isolated slave module
Control circuit
Power supply
generation
Connected load
24VDC external
power supply
24V 0V
24V 0V
24VL
0VL
0
1
n
DP DN
DP DN
Bridge module