46
6 MEMORY MAP
6.2 Lists of Remote Register Areas
When the CC-Link operation mode is Ver.2.00
The following table lists remote register areas when the CC-Link operation mode is Ver.2.00.
Remote registers when 4 stations are occupied
Both input and output of AnyWireASLINK use 32 words.
Set the addresses of slave modules within the range of 0 to 255.
n: Address assigned to the master station in the station number setting
CC-Link side remote register input
AnyWireASLINK
side input signal
CC-Link side remote register output
AnyWireASLINK
side output signal
Decimal
Hexadecimal
Decimal
Hexadecimal
RWrn+0
RWrn+0H
0 to 15
RWwn+0
RWwn+0H
0 to 15
RWrn+1
RWrn+1H
16 to 31
RWwn+1
RWwn+1H
16 to 31
RWrn+14
RWrn+EH
224 to 239
RWwn+14
RWwn+EH
224 to 239
RWrn+15
RWrn+FH
240 to 255
RWwn+15
RWwn+FH
240 to 255
RWrn+16
RWr(n+1)0H
Latest error code
storage area
RWwn+16
RWw(n+1)0H
Parameter access
setting
RWrn+17
RWr(n+1)1H
Latest error ID storage
area
RWwn+17
RWw(n+1)1H
Parameter access
target module ID
specification
RWrn+18
RWr(n+1)2H
Number of the IDs of
the connected modules
RWwn+18 to RWwn+23
RWw(n+1)2H to
RWw(n+1)7H
Use prohibited
RWrn+19
RWr(n+1)3H
Number of the error IDs
RWrn+20
RWr(n+1)4H
Number of the alarm
IDs
RWrn+21 to RWrn+23
RWr(n+1)5H to
RWr(n+1)7H
Use prohibited
RWrn+24
RWr(n+1)8H
RWwn+24
RWw(n+1)8H
Monitor command
specification area
RWrn+25 to RWrn+31
RWr(n+1)9H to
RWr(n+1)FH
RWwn+25 to RWwn+31
RWw(n+1)9H to
RWw(n+1)FH
Use prohibited