21
BOILER WATER SPECIFICATIONS
GENERAL MAINTENANCE
According to TS EN 12953-10 Boilers
Feeding and Boiler Water Quality standard, boiler water and feeding water specifications should
be as follows.
With a view to prevent damages that might occur due to rusting in heating installation, heating
water in drinking water quality should be used, chemical additives and/or aggressive waters in
terms of corrosion should not be used. Within water content to be filled in boiler and installation,
there should not be residue, wastes and unwanted solid particles. This sediment and dirt are
extremely harmful to the circulating pump. If you suspect that water is not clear, make sure to
install a filter before filling water.
Hardness of water to be used installation and boiler must be between (0-50) French hardness.
Limy water used in the system forms a layer of lime and mud in time on tube plate of boiler. This
lime and mud layer prevents water circulation and heat transfer, and deforms the boiler.
In this case, your device shall be out of warranty.
Heating boilers must undergo a general maintenance at least once a year. In general maintenance,
check the following considerations.
• Monitor operations of boiler fittings (thermostat, thermometer, hydrometer, manometer) all the
time, do the necessary controls, replace it if necessary. By putting thin mineral oil in thermometer
hives, healthier heat transfer must be ensured.
• Check sealing of all connections in the installation. Eliminate any leaks and reinforce seals of
valves if necessary.
• Sealing elements of boiler front large cover and front and rear smoke chest should be checked
continuously, if any leaks exist; clamping elements and bolts should be tightened in balance,
if leaks are not cut off, seal, cord should be changed or our authorized services must be
contacted. Bolts and nuts of clamping elements must have lubricated with grease.
• At the end of heating season, clean your boiler completely as in periodic cleaning.
• Achieve protection against oxidation by applying transformer oil or thin mineral oil on boiler
heating surfaces after cleaning.
• Water in boiler and installation should not be emptied if not required. At the end of season,
negative influence of corrosive elements on metal surfaces such as oxygen in water should be
eliminated by adding chemical additive to water in the system.
• Compare heating indicators with a calibrated thermometer. Check whether safety elements,
round safety pipes and safety valves work correctly.