Mirka® AIROS  •  77 mm (3"), 125 mm (5") & 150 mm (6")  •  Electrical manual

Example sequence for starting and stopping the tool:

•  Write 4 (0x0004) to the “Operation” register, this will set the motor drive to ON-state.
•  Write 4000 (0x0FA0) to the “Speed set-point” register, this will set the set-point speed to 4,000 rpm.
•   Write 1 (0x0001) to the “Operation” register, this will set the motor drive to RUN-state and the tool will start running.
•   Write 2 (0x0002) to the “Operation” register, this will set the motor drive to STOP-state and the tool will stop running.
•   Write 8 (0x0008) to the “Operation” register, this will set the motor drive to OFF-state.

Digital interface

The motor drive can also be controlled via the digital interface instead of Modbus RTU, but with the added drawback 
that there is no feedback when using the digital interface. To enable the digital interface, the JP12 jumper needs to be 
set. Make sure that the JP8, JP9, JP10 and JP11 jumpers are set as well.

Connector J5 is used as input for the digital interface. The input is considered high if a voltage between 15–33 VDC is 
applied to the input pin. The input is considered low if the voltage is below 12 VDC or if the input is left floating. The 
GND pin of connector J6 must be connected between the systems. The J6 connector can also be used to provide a 15 
VDC control voltage if needed.

Digital interface operations

J5.1 – DI1

J5.2 – DI2

J5.3 – DI3

J5.4 – DI4

Operation

0

0

0

0

Stopped

1

0

0

0

4,000 rpm

0

1

0

0

4,500 rpm

1

1

0

0

5,000 rpm

0

0

1

0

5,500 rpm

1

0

1

0

6,000 rpm

0

1

1

0

6,500 rpm

1

1

1

0

7,000 rpm

0

0

0

1

7,500 rpm

1

0

0

1

8,000 rpm

0

1

0

1

8,500 rpm

1

1

0

1

9,000 rpm

0

0

1

1

9,500 rpm

1

0

1

1

10,000 rpm

0

1

1

1

Run, no speed change

1

1

1

1

Run, no speed change

Self-test function

While holding down the S1 button the motor drive will perform a quick self-test. The alarm status flag will be set to 
6 (self-test running). The indicators D4 and D14 will blink green if temperatures and voltages are within the limits. If 
the temperatures or voltages are not within the limits then the indicators will blink red.

Reset function

The reset button S2 can be pressed momentarily to reset the motor drive. This is essentially the same as turning the 
power off and on again.

Summary of Contents for AIROS

Page 1: ......

Page 2: ...ver any damage caused or resulting from transport receipt of delivery installation commissioning misuse neglect in usage or maintenance accidents exposure to extreme unacceptable ambient temperature a...

Page 3: ...way addon module J2 J1 J5 J6 J3 J4 General Connect the 48 VDC power supply to the motor drive J2 connector Connect the tool to the motor drive J3 and J7 connector Modbus RTU interface Use the J1 conne...

Page 4: ...Dimensions Motor drive 72 x 30 x 200 mm W x H x D Motor drive mounted in DIN rail holder 95 x 55 x 210 mm W x H x D Safety instructions Electrical installation must be carried out by a competent elect...

Page 5: ...It is recommended to use 10 mm ferrules with plastic sleeve for each wire that is attached to any of the connectors The wires can then easily be pushed into the connectors and released with the help...

Page 6: ...lave address indicator bit 1 D3 Speed set point indicator lit if 5 000 rpm Modbus RTU slave address indicator bit 2 D4 Tool status indicator Lit red when the tool is stopped lit green when the tool is...

Page 7: ...Jumper description Jumpers Default Description JP1 Not set Reserved for future use JP2 Not set If set a terminating resistor of 270 is connected across Modbus RTU pins A and B JP3 Not set If set a pu...

Page 8: ...TU over RS 485 is used to communicate with the motor drive The motor drive is configured as a Modbus RTU slave device and the default slave address is 86 The slave address can be changed if it conflic...

Page 9: ...ber of times the run time has been more than 60 seconds 30012 Uint16 Usage count medium The number of times the run time has been between 20 and 60 seconds 30013 Uint16 Usage count short The number of...

Page 10: ...ilscher NT 50 RS EN gateway can be used The gateway is connected to the motor drive via the DSUB 9 connector on the gateway and the J1 connector on the motor drive Below is the pinout for the DSUB 9 X...

Page 11: ...ly monitor the average speed average current tool temperature motor drive temperature and the alarm status flag This will help to detect if there are any issues present during operation Profinet I O t...

Page 12: ...is considered high if a voltage between 15 33 VDC is applied to the input pin The input is considered low if the voltage is below 12 VDC or if the input is left floating The GND pin of connector J6 mu...

Page 13: ...before starting the new tool Protection features The motor drive will momentarily slow down the tool to 4 000 rpm if the motor drive temperature rises above 117 C or the tool temperatures rises above...

Page 14: ...ave address set the JP13 jumper and use indicators D2 D3 D17 D22 to read the current address Profinet I O gateway communication is not working Check the gateway network configuration Check the gateway...