Mirka® AIROS  •  77 mm (3"), 125 mm (5") & 150 mm (6")  •  Electrical manual

Mirka® AIROS  •  77 mm (3"), 125 mm (5") & 150 mm (6")  •  Electrical manual 

11

Siemens TIA Portal V14 gateway mapping example

Below is a screenshot from TIA Portal V14 showing how the gateway can be mapped into the system. Use the GSDML 
file that is downloadable from the Hilscher website to add support for the Hilscher NT 50-RS-EN gateway into your 
system.

Basic operation for Modbus RTU

The motor drive must be in ON-state before the tool can be started. The very first command that should be sent to the 
motor drive is the ON-state command. It is not mandatory to send the OFF-state command before removing power 
from the motor drive.

When the motor drive is in ON-state the speed set-point value can be written and the state can be set to RUN-state by 
sending the RUN-state command. This will cause the tool to run at the set-point speed. To stop the tool, set the motor 
drive to STOP-state by sending the STOP-state command.

It is recommended to continuously monitor the average speed, average current, tool temperature, motor drive 
temperature and the alarm status flag. This will help to detect if there are any issues present during operation.

Profinet I/O to Modbus RTU signal mapping

Name

Modbus  

register

Data  

length

Trigger

Profinet  

I/O slot

Data  

length

SetRelay

00012

1 coil

Changed data

1

1 byte out

SetSpeedRegister

40011

1 register

Changed data

2

1 word out

SetOperationRegister

40012

1 register

Changed data

3

1 word out

DeviceName

40001–40010

10 registers

Cyclically 10 sec.

4

10 words in

CommonInputs

30017–30020

4 registers

Cyclically 1 sec.

5

4 words in

MiscInputs

30001–30016

16 registers

Cyclically 5 sec.

6

16 words in

AlarmStatus

30047

1 register

Cyclically 1 sec.

7

1 word in

FirmwareVersion

30021–30030

10 registers

Cyclically 10 sec.

8

10 words in

PartVersion

30031–30040

10 registers

Cyclically 10 sec.

9

10 words in

SerialNumber

30041–30046

6 registers

Cyclically 10 sec.

10

6 words in

GetSpeedRegister

40011

1 register

Cyclically 1 sec.

11

1 word in

GetOperationRegister

40012

1 register

Cyclically 1 sec.

12

1 word in

ReadCoils

00001–00012

12 coils

Cyclically 1 sec.

13

2 bytes

Summary of Contents for AIROS

Page 1: ......

Page 2: ...ver any damage caused or resulting from transport receipt of delivery installation commissioning misuse neglect in usage or maintenance accidents exposure to extreme unacceptable ambient temperature a...

Page 3: ...way addon module J2 J1 J5 J6 J3 J4 General Connect the 48 VDC power supply to the motor drive J2 connector Connect the tool to the motor drive J3 and J7 connector Modbus RTU interface Use the J1 conne...

Page 4: ...Dimensions Motor drive 72 x 30 x 200 mm W x H x D Motor drive mounted in DIN rail holder 95 x 55 x 210 mm W x H x D Safety instructions Electrical installation must be carried out by a competent elect...

Page 5: ...It is recommended to use 10 mm ferrules with plastic sleeve for each wire that is attached to any of the connectors The wires can then easily be pushed into the connectors and released with the help...

Page 6: ...lave address indicator bit 1 D3 Speed set point indicator lit if 5 000 rpm Modbus RTU slave address indicator bit 2 D4 Tool status indicator Lit red when the tool is stopped lit green when the tool is...

Page 7: ...Jumper description Jumpers Default Description JP1 Not set Reserved for future use JP2 Not set If set a terminating resistor of 270 is connected across Modbus RTU pins A and B JP3 Not set If set a pu...

Page 8: ...TU over RS 485 is used to communicate with the motor drive The motor drive is configured as a Modbus RTU slave device and the default slave address is 86 The slave address can be changed if it conflic...

Page 9: ...ber of times the run time has been more than 60 seconds 30012 Uint16 Usage count medium The number of times the run time has been between 20 and 60 seconds 30013 Uint16 Usage count short The number of...

Page 10: ...ilscher NT 50 RS EN gateway can be used The gateway is connected to the motor drive via the DSUB 9 connector on the gateway and the J1 connector on the motor drive Below is the pinout for the DSUB 9 X...

Page 11: ...ly monitor the average speed average current tool temperature motor drive temperature and the alarm status flag This will help to detect if there are any issues present during operation Profinet I O t...

Page 12: ...is considered high if a voltage between 15 33 VDC is applied to the input pin The input is considered low if the voltage is below 12 VDC or if the input is left floating The GND pin of connector J6 mu...

Page 13: ...before starting the new tool Protection features The motor drive will momentarily slow down the tool to 4 000 rpm if the motor drive temperature rises above 117 C or the tool temperatures rises above...

Page 14: ...ave address set the JP13 jumper and use indicators D2 D3 D17 D22 to read the current address Profinet I O gateway communication is not working Check the gateway network configuration Check the gateway...

Page 15: ......

Page 16: ...India Pvt Ltd Italy Mirka Italia s r l Cafro S p A Mexico Mirka Mexicana S A de C V Russia Mirka Rus LLC Singapore Mirka Asia Pacific Pte Ltd Spain Mirka Ib rica S A U Sweden Mirka Scandinavia AB Tur...

Reviews: