72
Pre-Programmed Modes
12.2.4 How the Panel Works in Mode 2
•
Activation of either Z-1 or Z-2 turns NAC-1 on steady.
•
Activation of either Z-1 or Z-2 changes the Hazard Area 1 state from Idle into Alarm
directly. NAC-1 turns on steady. NAC-2 turns on Temporal. Release Timer-1 is started.
•
Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn
on steady.
•
Activation of Z-6 starts Manual-release Timer 1 (MDT-1) in any situation. NAC-1 turns on
steady. NAC-2 turns on Temporal. Upon the expiration of MDT-1, RAC-1 and RAC-2
turn on.
•
During Hazard Alarm state, if Z-5 is pressed, Release Timer-1 is held. After releasing of
Z-5, Release Timer-1 resumes running and Release Timer value depends on Abort
Delay Type.
•
Activation of Z-3 turns both NAC-1 and NAC-2 on steady.
•
Activation of Z-4 can be indicated on NAC-2 at 20BPM, if enabled.