41
Indicators, Controls and Operations
9.1.14 ALM/SUP/TBL/BLDG AUDIBLE SIL (Buzzer Silence)
Flashes amber at a slow rate when the buzzer is silenced.
9.1.15 Pre Release
Flashes red at a fast rate, when the release timer is started turns off when the release timer
expires or the system is reset.
9.2
Menu Buttons
To use the menu buttons you will need to install the CFG-300 configuration tool. See
Using the CFG-300 Tool on page 48
31 for details.
Menu Button
9.3
Switches and Common Indicators
The FR-320 Series panel is a six-zone panel with four output circuits. The circuits are
arranged in the following configuration:
9.3.1
Zone 1 to Zone 4
•
Alarm LED (red) turns on steady when an alarm is detected
•
Supervisory LED (amber)turns on steady when the circuit is active
•
Trouble LED (amber)turns on at slow flash rate when in trouble or bypassed
9.3.2
Zone 5 and Zone 6
•
Alarm LED & Trouble LEDThe zone type and LED behavior varies upon the
configuration. Steady when turned on.
Menu
Button
Pressing
and entering the passcode will allow you to enter the command menu.
Info
Button
When the system is off-normal, press
to display extra information of the event.
Enter
Button
Pressing this button to select a menu option or to confirm a menu operation.
Cancel
Button
To return to previous menu in the configuration or command mode.
Zone 1
Input circuit
Zone 2
Input circuit
Zone 3
Input circuit
Zone 4
Input circuit
Zone 5
Manual Release switches or Abort switches or individual switch
Zone 6
Manual Release switches or individual switch
Out 1
NAC1
Out 2
NAC2
Out 3
Releasing circuit 1
Out 4
Releasing circuit 2 or NAC3 in some applications
M
M
?
?
X
Summary of Contents for FR-320 Series