35
Field Wiring
7.8
Wiring Tables and Information
7.9
Four-Wire Smoke Power (regulated)
Four-wire smoke power is provided for four-wire smoke detectors. This filtered supply is
supervised therefore a short will disconnect the power and the common trouble is active. The
power is reconnected after the 'RESET' key is pressed. See
Table 3 Initiating Circuit Wiring Distances
WIRE GAUGE
MAXIMUM WIRING RUN TO LAST DEVICE
AWG
FEET
METERS
22
2990
910
20
4760
1450
18
7560
2300
16
12000
3600
14
19000
5800
12
30400
9200
Notes:
For Class A the maximum wiring run to the last device is divided by two.
Maximum loop resistance should not exceed 100 ohms.
Maximum capacitance of 0.5uF total on each initiating circuit.
Table 4 Indicating Circuit Wiring Distances
TOTAL
SIGNAL
LOAD
MAXIMUM WIRING RUN TO LAST DEVICE (ELR)
MAX. LOOP
RESISTANCE
18AWG
16AWG
14AWG
12AWG
Amperes
ft
m
ft
m
ft
m
ft
m
Ohms
0.06
2350
716
3750
1143
6000
1829
9500
2895
30
0.12
1180
360
1850
567
3000
915
4720
1438
15
0.30
470
143
750
229
1200
366
1900
579
6
0.60
235
71
375
114
600
183
950
289
3
0.90
156
47
250
76
400
122
630
192
2
1.20
118
36
185
56
300
91
470
143
1.5
1.50
94
29
150
46
240
73
380
115
1.2
1.70
78
24
125
38
200
61
315
96
1.0
Notes:
For Class A wiring the resistance in ohms is multiplied by two.
Maximum voltage drop should not exceed 1.8 volts.
i
i