Pre-Programmed Modes
12.11 Mode 11: Agent Release, Single Hazard, Cross-zoned,
Combined Release
12.11.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area1, cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area1, cross-zoned)
•
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
•
Detection Zone -4: Supervisory (Default non-latching)
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release
•
NAC -1: Signal, indicate the Hazard Area1 status.
•
NAC -2: Signal, indicate the Hazard Area1 status.
•
RAC -1: Releasing Circuit
•
RAC -2: Releasing Circuit
12.11.2 Hazard Configuration
•
Default Release Timer Value: 60 seconds
•
Default Manual Release Delay: 0 seconds
•
Default Abort Delay Type: Standard UL.
•
Soak Timer Value: 0 seconds (continuous)
12.11.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
Hazard Idle: Off
•
Hazard Alert: Steady
•
Hazard Alarm: 60BPM
•
Hazard Release: Steady
•
Default NAC code of supervisory is 20 BPM
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
WF
Supv
AB
MR
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
Out2
Signal
Escalating
X
(X)
X
X
Out3
Rel.
Releasing
X
X
Out4
Rel.
Releasing
X
X
RLS TMR 1 Started
X
RLS Tmr 1 Interrupted
X
RLS Tmr 1 Cancelled
X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled