background image

FA-262 Installation & Operator’s Manual

16

5.0 Panel Operation

5.1 Operating Sequences

This section describes how the panel functions under various conditions. The choices you make in panel 
programming will also affect how the panel operates. Please see  for information on how to program the panel, 
and descriptions of each of the programming options.

5.2 General Zone Fire Alarms

Zone alarms have priority over all other annunciation. When an alarm occurs, the following happens:

•The corresponding zone alarm LED begins flashing, the common alarm LED turns on steady, and the alarm 
relay turns on.
•If a trouble was present on that zone then the zone trouble LED turns off. If the trouble buzzer is audible 
then it also turns off. 
•The NACs sound in a steady or temporal pattern, depending on the option selected (see “NAC Temporal/
Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25). 
•If enabled, the silence inhibit timer begins counting down (see “Signal Silence Inhibit Timer” on page 26). If 
the silence inhibit timer is enabled, the panel cannot be silenced for 60 seconds following the first fire alarm. 
Subsequent fire alarms do not restart or extend this timer. While the signal silence inhibit timer is counting 
down, if the Silence Alarm button is pressed the panel will sound a 1 second ‘error tone’ on the common 
trouble buzzer.
•The NACs remain on until silenced with the Silence Alarm button, or if the automatic alarm silence is 
enabled, until the thirty minute bell timer runs out (see “Automatic Signal Silence” on page 25). If the 
automatic silence timer is enabled, the panel will automatically silence the NACs 30 minutes after the

 last

 

fire alarm. Each zone alarm will restart the timer, giving a full 30 minutes after the last alarm before the NACs 
are silenced.

• Once the NACs are silenced the signals silenced LED turns on and any flashing zone alarm LEDs turn on 

steady. The common trouble LED and trouble relay also turn on and, if the NACs have been silenced 

automatically

, the buzzer will sound at a rate of ½ second ON/OFF.

•Any additional zone alarms that occur while the panel is in alarm will reset the auto alarm silence timer and 
turn on the NACs, but the panel will not restart the 60 second silence inhibit timer. 
•The zone alarm LEDs, common alarm LED and alarm relay will remain on steady until a system reset is 
performed.

5.3 Waterflow Alarms

If the Waterflow Silence option is turned off (see “Silence Waterflow Alarms” on page 26), when a waterflow 
zone (type 03) initiates an alarm the NACs cannot be silenced until all waterflow zones are returned to normal. 
If all waterflow zones return to normal after the 30 minute automatic signal silence timer has expired, then the 
panel will silence the NACs. 

If the Waterflow Silence option is turned on, then an alarm on a waterflow zone is treated like any other fire 
alarm.

Waterflow alarms may be delayed by 60 seconds to prevent false alarms from surges in the sprinkler system. 
The delay is common to all zones programmed as ‘waterflow’, type 03 zones. If the delay is not used, all 
waterflow alarms will be instant.

Note:

 

A manual signal silence will not initiate the trouble buzzer. Only the common trouble LED and 

signals silenced LED are turned on. 

Summary of Contents for FA-262

Page 1: ...FA 262 Fire Alarm Control Panel LT 2015MIR Rev 1 Frbruary 2008 Installation and Operator s Manual Advanced Life Safety Solutions...

Page 2: ......

Page 3: ...cations 10 4 2 Connecting NAC Devices Class A and Class B 12 5 0 Panel Operation 16 5 1 Operating Sequences 16 5 2 General Zone Fire Alarms 16 5 3 Waterflow Alarms 16 5 4 Supervisory Zone Alarms 17 5...

Page 4: ...r s Manual ii 9 0 Appendix Table of Compatible Smoke Detectors 33 9 1 Smoke Detector Bases 35 9 2 Compatible 4 Wire Smoke Detectors 35 9 3 Compatible Horns Strobes 36 FCC Compliance Statement 38 Warra...

Page 5: ...nsions 9 Figure 7 Knockout Locations 9 Figure 8 FA 262 Terminal Descriptions 10 Figure 9 Connecting 2 Wire Alarm Initiating Devices 11 Figure 10 Connecting 4 Wire Smoke Detectors 12 Figure 11 Connecti...

Page 6: ......

Page 7: ...e Alarm Systems Information provided with this unit is intended as a guide Installation of this equipment optional system components alarm initiating devices and notification appliances must follow th...

Page 8: ...amage or extended power outages has occurred 1 5 Standby Power The FA 262 provides standby battery support for lead acid rechargeable batteries The required capacity of the standby batteries must be c...

Page 9: ...ain board UDACT 286 Dual line dialer Communicates all alarms supervisory and trouble conditions to a Central Station using Contact ID SIA or 10 20 BPS communication formats Programmable using the MR 2...

Page 10: ...nk insert Zone designations can be written directly on the insert or can be created using Word for Windows printed on Avery label 5167 and applied to the insert CPU FAULT Figure 1 FA 262 cabinet with...

Page 11: ...gauge and wire run distances for the connected components initiating devices indicating devices and secur bus connected components Review the programming section of this manual and determine the opera...

Page 12: ...ose totals in the standby and alarm columns 5 Add up all the current drawn from the AUX output in the standby and alarm mode and put those totals in the standby and alarm columns 6 Add up all the curr...

Page 13: ...x RM 263 Standby 0 x Alarm 24 x 5 AUX Standby x Alarm x 6 Total standby and alarm current mA mA 7 Divide standby mA and alarm mA by 1000 Amp Amp 8 Select standby time required 24 or 60 Hr Hr 9 Standby...

Page 14: ...temperature 32 F to 122 F 0 C to 50 C Humidity 95 RH non condensing Close to a source of unswitched AC power 3 2 Panel Assembly and Modules Locations The panel comes completely assembled from the fact...

Page 15: ...FA 262 Installation Operator s Manual 9 3 3 Mounting the FA 262 Figure 6 Mounting Dimensions Figure 7 Knockout Locations Dimensions in inches...

Page 16: ...ripple power limited Aux power shorts must be restored by removing all Aux Power loading COM Auxiliary common power return unswitched 24 VDC 500 mA max SCOM Auxiliary common power return switched ope...

Page 17: ...the de energized state Contacts are rated 30 VDC 2 Amps max Z1 Zone 1 positive input Z1 Zone 1 negative input Zone output is 24 VDC nominal to power 2 wire smoke detectors Maximum current draw is 60 m...

Page 18: ...l loop wire resistance is 100 ohms Zone Wiring Chart 4 2 Connecting NAC Devices Class A and Class B Figure 11 Connecting NAC Devices Class B Figure 12 Connecting NAC Devices Class A Wire Gauge Distanc...

Page 19: ...9 769 235 1 250 381 2 70 0 75 205 63 325 99 513 156 833 254 2 00 1 00 154 47 244 74 385 117 625 191 1 60 1 25 123 38 195 59 308 94 500 152 1 30 1 50 103 31 163 50 256 78 417 127 Note This chart is bas...

Page 20: ...62 384 3 200 976 5 080 1 549 8 000 2 439 45 842 256 2 135 651 3 385 1 032 5 340 1 628 60 631 192 1 600 488 2 540 774 4 000 1 220 75 505 154 1 280 390 2 030 619 3 200 976 90 421 128 1 065 325 1 690 515...

Page 21: ...ted to the Secur bus All devices are supervised See section for adding and deleting devices on the Secur bus Remix 1 25 ohms Immix Amps Distance Remix 1 000 feet 2 wire resistance in ohms per 1 000 fe...

Page 22: ...nal Silence on page 25 If the automatic silence timer is enabled the panel will automatically silence the NACs 30 minutes after the last fire alarm Each zone alarm will restart the timer giving a full...

Page 23: ...ble and it goes into alarm the zone trouble LED is extinguished until that zone is restored and the panel has been reset The common trouble LED will remain on steady until all supervisory alarms have...

Page 24: ...ns on Ground on extended conductor turns on sounds second on off deactivates Ground LED turns on AC fails completely or is low for more than 10 seconds brownout turns on sounds second on off deactivat...

Page 25: ...e or more zones is still in alarm after the reset period the panel will activate the NACs as programmed If there are no alarms but one or more Supervisory zones is still off normal after the reset per...

Page 26: ...remote connection is not activated 3 To return the system to normal operation press the Walk Test button If you do not press the Walk Test button the system will return to normal operation after one h...

Page 27: ...f all zone fire alarms are restored Only NAC2 can be set in this mode Class A operation selections If the panel NACs are set for class A operation then there is only one NAC In this configuration the...

Page 28: ...as shown below Figure 17 Locating the Walk Test Switch 2 Press and hold the Walk Test Switch for two seconds The common trouble buzzer and common trouble LED turn on and pulse second on off 3 Press a...

Page 29: ...move to the next programming section when you press the Silence Trouble button Example in the Zone 1 programming sub section pressing Silence Alarm will scroll through each zone type setting null zone...

Page 30: ...condition Zone type 03 Waterflow zone This zone type is intended for waterflow alarm initiating contact devices only Do not mix other alarm initiating devices on this zone For Waterflow delay use act...

Page 31: ...ED on steady Automatic Signal Silence If Automatic Signal Silence is enabled 30 minutes after the last fire alarm on the system the panel restores the NACs to normal alarms are silenced If another ala...

Page 32: ...et the One Man Walk Test to be either audible or silent If the One Man Walk Test is set for audible then the following will occur On a fire or Supervisory alarm restoral the bells will pulse ONCE On a...

Page 33: ...0 60 Hz Option Reset Section Programming All common trouble LEDs flashing To Enter this Programming Section 1 Enter the installer programming mode section 0 2 Press and hold the System Reset button fo...

Page 34: ...e Fault Restore Flashing NAC1 Trouble LED NAC 1 Trouble Steady NAC1 Trouble LED NAC 1 Trouble Restore Flashing NAC2 Trouble LED NAC 2 Trouble Steady NAC2 Trouble LED NAC 2 Trouble Restore Flashing Bat...

Page 35: ...operly and if it is it may take up to 24 hours to recharge the batteries Once the battery is charged the battery fault LED will go OFF 7 3 Default Operation On first power up all programmable features...

Page 36: ...gh the settings for each programming section e g to change the zone type or to turn an option on or off 4 Press Silence Trouble to move to the next programming section e g to move from zone 1 to zone...

Page 37: ...g Section 1 NAC1 LED on steady on page 25 Factory default 8 4 NAC Auto silence Strobe Programming Section 2 Please see NAC Auto silence and Strobe Programming Section 2 NAC2 LED on steady on page 25 F...

Page 38: ...ease see Waterflow Programming Section 4 Ground Fault LED on steady on page 26 Factory default 8 7 50 60 Hz Option Section 5 Factory default ZONE ALARM LED On Programming Section Settings 1 Signal Sil...

Page 39: ...ith Thermal 2 wire 12 24VDC 01 25 System Sensor 2400AT A N A N A Photoelectric with Thermal and Horn 2 wire 24VDC 01 25 System Sensor 2400AIT A N A N A Photoelectric with isolated Thermal and Horn 2 w...

Page 40: ...B401 B401B DH400 N A Plug in Low Profile Ion 01 25 System Sensor 2151 2151A A B401 B401B DH400 N A Plug in Low Profile Photo 01 25 System Sensor 2100S A N A N A 2 wire direct wire Photoelectric 01 25...

Page 41: ...em Sensor B116LP N A 2 wire base 24VDC form contact 25 System Sensor DH400 N A Duct Detector Mount 25 System Sensor RMK400 N A Recessed mount kit for Series 400 Manufacture r Models System Sensor 1124...

Page 42: ...75 20 30 S24110 W A S 110 20 30 H24 W A H 20 30 MDL W A Module 20 30 No suffix Red suffix W White suffix A Canadian version Gentex Type Cd Voltage FWR GEH24 H 20 31 GES24 15 S 15 20 31 GES24 15 75 S...

Page 43: ...FR W H S 75 20 31 NS4 24110W FR W H S 110 20 31 NS 2 wire NS4 4 wire AS 2415W FR W S 15 20 31 AS 241575W FR W S 15 75 20 31 AS 2430W FR W S 30 20 31 AS 2475W FR W S 75 20 31 AS 24110W FR W S 110 20 3...

Page 44: ...there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turnin...

Page 45: ...dition and installed correctly If a device operates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length a...

Page 46: ...awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification...

Page 47: ...provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintenance damage arisi...

Page 48: ...ket price of the replacement product will be charged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2007 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Reviews: