background image

Warranty and Warning Information

18

testing should include all sensing devices, keypads, consoles, alarm indicating devices and any 
other operational devices that are part of the system.

NOTE TO USERS:

All Mircom Systems have been carefully designed to be as effective as possible. However, there are 
circumstances where they may not provide protection. Some reasons for system failure include the following.  
The end user can minimize the occurrence of any of the following by proper training, testing and maintenance 
of the Mircom Systems: 

6.

Inadequate Testing and Maintenance.  

It is

 

imperative that the systems be periodically tested 

and subjected to preventative maintenance.  Best practices and local authority having jurisdiction 
determine the frequency and type of testing that is required at a minimum.  Mircom System may 
not function properly, and the occurrence of other system failures identified below may not be 
minimized, if the periodic testing and maintenance of Mircom Systems is not completed with 
diligence and as required.  

7.

Improper Operation.

  It is important that all system users be trained in the correct operation of the 

alarm system and that they know how to respond when the system indicates an alarm.  A Mircom 
System

 

may not function as intended during an emergency situation where the user is unable to 

operate a panic or emergency switch by reason of permanent or temporary physical disability, 
inability to reach the device in time, unfamiliarity with the correct operation, or related 
circumstances.

8.

Insufficient Time.  

There may be circumstances when a Mircom System will operate as intended, 

yet the occupants will not be protected from the emergency due to their inability to respond to the 
warnings in a timely manner. If the system is monitored, the response may not occur in time 
enough to protect the occupants or their belongings.

9.

Carelessness or Safety Hazards. 

 Moreover, smoke detectors may not provide timely warning of 

fires caused by carelessness or safety hazards such as smoking in bed, violent explosions, 
escaping gas, improper storage of flammable materials, overloaded electrical circuits or children 
playing with matches or arson.

10.

Power Failure.  

Some Mircom System

 

components require adequate electrical power supply to 

operate.  Examples include: smoke detectors, beacons, HVAC, and lighting controllers.  If a device 
operates only by AC power, any interruption, however brief, will render that device inoperative 
while it does not have power.  Power interruptions of any length are often accompanied by voltage 
fluctuations which may damage Mircom Systems or other electronic equipment.  After a power 
interruption has occurred, immediately conduct a complete system test to ensure that the system 
operates as intended.

11.

Battery Failure.  

If the Mircom System or any device connected to the system operates from 

batteries it is possible for the batteries to fail. Even if the batteries have not failed, they must be 
fully charged, in good condition, and installed correctly. Some Mircom Systems use replaceable 
batteries, which have a limited life-span. The expected battery life is variable and in part 
dependent on the device environment, usage and type. Ambient conditions such as high humidity, 
high or low temperatures, or large temperature fluctuations may reduce the expected battery life.  
Moreover, some Mircom Systems do not have a battery monitor that would alert the user in the 
event that the battery is nearing its end of life.  Regular testing and replacements are vital for 
ensuring that the batteries function as expected, whether or not a device has a low-battery 
monitor.

12.

Physical Obstructions.  

Motion sensors that are part of a Mircom System must be kept clear of 

any obstacles which impede the sensors’ ability to detect movement.  Signals being 
communicated by a Mircom System may not reach the receiver if an item (such as metal, water, or 
concrete) is placed on or near the radio path.  Deliberate jamming or other inadvertent radio signal 
interference can also negatively affect system operation.  

Summary of Contents for FA-103

Page 1: ...FA 103 and FA 106 Fire Alarm Control Panels LT 1200 Rev 2 March 2018 Installation and Operation Manual Advanced Life Safety Solutions...

Page 2: ......

Page 3: ...ation 9 Trouble Indicators and Controls 11 Common Trouble LED 11 Buzzer Buzzer Silence Pushbutton 11 Detection Zone Trouble LED 11 Ground Fault LED 11 Battery Fault LED 11 Detection Zone Disable 11 Se...

Page 4: ...Figure 3 Conduits for Wiring 4 Figure 4 Setting the DIP Switch functions 5 Figure 5 A C Power and Battery Connection 6 Figure 6 Circuit Board Layout 7 Figure 7 Detection and signal wiring 8 Figure 8 A...

Page 5: ...pt the FA 103 is depopulated and has terminal connections for three detection zones only Use of the reference the panel will apply to both models FA 106 and FA 103 Models available are Mechanical Inst...

Page 6: ...2 Figure 1 Backbox and flush trim mounting details 13 3 4 12 3 4 1 11 16 Optional flush mounting trim model FA 102TR Four 7 32 dia mounting holes 2 7 8 7 1 8 1 1 4 10 3 8...

Page 7: ...3 Figure 2 Assembly of FA 106 and FA 103 Fire Alarm Panels Inner Dead Front Outer Front Door...

Page 8: ...dedicated conduit in knockouts A or B shown in Figure 3 All other circuits are current limited and must be run through knockouts C or D Figure 3 Conduits for Wiring Clearances The controls shall be n...

Page 9: ...age which will be connected to the fire alarm panel INPUT VOLTAGE DIP SWITCH SW12 7 DIP SWITCH SW12 8 120V OFF OFF 240V ON OFF 220V OFF ON 1 2 3 4 5 6 7 8 ON Alarm Relay ON Disconnects the Alarm Relay...

Page 10: ...r contact location and designation Remote Annunciation Annunciation outputs are provided for connection to an RTI 1 Remote Trouble indicator Refer to Figure 8 on page 10 for wiring instruction A C Pow...

Page 11: ...ZONES 1 TO 6 DIP SWITCH SW12 ALARM LED per Zone TROUBLE LED per Zone Space for Detection Zone label NAC active red LED and NAC yellow trouble LED per NAC zone The battery fuse protects against batter...

Page 12: ...24VDC Regulated 50mA max alarm 24VDC Regulated 50mA max alarm 24VDC Regulated 50mA max alarm 24VDC Regulated 50mA max alarm 24VDC Regulated 50mA max alarm 24VDC Regulated 50mA max alarm 24V RMS FWR 1...

Page 13: ...Run to Last Device ELR AWG ft m 18 7560 2300 16 12000 3600 14 19000 5800 12 30400 9200 Note Maximum loop resistance should not exceed 100 ohms Total Signal Load Maximum Wiring Run to Last Device ELR...

Page 14: ...zzer 24V 24VDC 250mA max Resettable or Always ON 24V 24VDC 250mA max GND Not used GND ELR 3 9K 1 2 W RTI 1 BLACK BLUE RED WHITE Resettable Aux 24V DC Resettable Aux 24V DC TO DETECTION ZONE POWER LAST...

Page 15: ...across into the front display Ground Fault LED Any ground fault of 1K ohms or less will flash the yellow Ground Fault LED flash the yellow Common Trouble LED and sound the common trouble buzzer inter...

Page 16: ...NOTE The CPU FAIL LED will not illuminate during Lamp Test System Checkout Before turning the power on 1 Check all external wiring for opens shorts or grounds 2 Check that transformer cables are secu...

Page 17: ...rm 1 zone active 95mA 2 zone active 136mA 3 zone active 177mA 4 zone active 218mA Zones 4 to 6 not available on the FA 103 5 zone active 259mA 6 zone active 300mA Maximum current of Aux Power and Dete...

Page 18: ...ircom System Sensor i3 MIR 525 30 C2W BA c w base 30 MIR 525T 30 C2WT BA c w base 30 Apollo System Sensor Series 60A Bases 45681 200 220 232 251 1400A 30 Series 65A Bases 45681 255 256 257 258 2400A 2...

Page 19: ...2451A B401A 25 DS282TH 30 2451THA B401A 25 Siemens 5451A B401BA 25 HI121 DB 11 DB 11C 20 5451A B401A 25 OH121 DB 11 DB 11C 20 5451A B406BA 25 OP121 DB 11 DB 11C 20 Sentrol ESL 429CST 30 429CRT 30 713...

Page 20: ...must provide a dedicated continuous power without provision of any disconnect devices Use 12 AWG wire with 600 volt insulation and proper over current circuit protection that complies with the local...

Page 21: ...fe insurance Nor is the system a substitute for property owners renters or other occupants to act prudently to prevent or minimize the harmful effects of an emergency situation Building automation sys...

Page 22: ...ay not provide timely warning of fires caused by carelessness or safety hazards such as smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical cir...

Page 23: ...nts Alarm notification appliances such as sirens bells horns or strobes may not warn or waken a sleeping occupant if there is an intervening wall or door It is less likely that the occupants will be a...

Page 24: ...Tel 888 660 4655 905 660 4655 Fax 905 660 4113 Mircom 2018 Printed in Canada Subject to change without prior notice www mircom com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 6...

Reviews: