Appendix B: Compatible Devices
FA-106 and FA-103 Underwriters Laboratories Canada ULC Listed 2-Wire Smoke
Detectors
Notes:
• Reset time, hold for five seconds minimum.
• Total standby current of all detectors must not exceed 3 mA.
• Two-wire smoke detectors can be mixed or matched with different models on the
same Initiating Circuit as long as the total standby current of all detectors does not
exceed 3mA.
Make Model / Base
Maximum # of
devices per
circuit
Make Model / Base
Maximum # of
devices per
circuit
Mircom
System Sensor i3
MIR-525
30
C2W-BA c/w base
30
MIR-525T
30
C2WT-BA c/w base
30
Apollo
System Sensor
Series 60A Bases 45681-200,-220,-232,-251
1400A
30
Series 65A Bases 45681-255,-256,-257,-258
2400A
25
55000-325
30
1451A/B401BA
25
55000-326
30
2451A/B401BA
25
55000-327
30
1100
25
55000-328
30
1151A/ B110LPA
25
Hochiki
1151A/ B116LPA
25
DCD-135/HSC-220R
12
1451A/B401A
25
DCD-135/NS6-220
12
1451A/ B406BA
25
DCD-190/HSC-220R
12
1451DH/ DH400
25
DCD-190/NS4-220
12
2100A
30
DCD-190/NS6-220
12
2100TA
30
SU-24/HSC-220R
12
2151A/ B110LPA
15
SU-24/NS4-220
7
2151A/ B116LPA
25
SU-24/NS6-220
7
2400THA
25
SLR-24/HSC-220R
12
2451A / B401BA
25
SLR-24/NS4-220
12
2451A / B406BA
25
SLR-24/NS6-220
12
2451A / DH400
25