7
6
The AC normal icon illuminates when the UPS is on and operating in
the AC normal mode. The AC normal icon will extinguish when operat-
ing in the Battery mode.
The On-Battery icon illuminates when the UPS is operating in the Bat-
tery mode. The On-Battery icon will extinguish when operating in the
AC normal.
The Weak/Bad Battery icon illuminates when the UPS detects a weak
battery, bad battery or if the battery is disconnected. The Weak/Bad
Battery icon is extinguished when the battery's condition is good.
The Fault icon illuminates when the UPS detects an internal fault. The
Fault icon is extinguished when the UPS is operating properly.
The Site Wiring icon (120V models) illuminates when the UPS de-
tects a site wiring problem. The SWF icon is extinguished when the
UPS is connected to proper site wiring.
The Load Level Bar Graph operates as follows:
LED #1: When the attached load is >20% the LED will illuminate.
LED #2: When the attached load is >40% the LED will illuminate.
LED #3: When the attached load is >60% the LED will illuminate.
LED #4: When the attached load is >80% the LED will illuminate.
LED #5: When the attached load is >100% the LED will illuminate.
The Battery Capacity Bar Graph operates as follows:
LED #1: When the battery capacity is >20% the LED will illuminate.
LED #2: When the battery capacity is >40% the LED will illuminate.
LED #3: When the battery capacity is >60% the LED will illuminate.
LED #4: When the battery capacity is >80% the LED will illuminate.
LED #5: When the battery capacity is >100% the LED will illuminate.
NOTE:
The LCD backlight will illuminate for 20-seconds when the UPS switches
to the Battery mode. When the UPS has an event and/or an error code the LCD
backlight will turn on and remain on to alert the user that an event has occurred.
Chapter 2: Controls and Indicators
The UPS output is off
bPS
EPo
RPo (E24)
ECo
PAS
off
The UPS output has been turned on
The UPS is operating in the Bypass mode
The UPS is operating in the Economy mode
The battery test Failed
The UPS has been shutdown due to the Remote Power Off function
bAd
The battery test Passed
The UPS has been shutdown due to the Emergency Power Off function
on
The Multi-Function On/Off/Test Button functions as follows:
When the UPS is Off, press and release the On/Off/Test button during
the audible alarm's first beep to turn the UPS On.
When the UPS is On, press and release the On/Off/Test button during
the audible alarm's first beep to turn the UPS Off.
When the UPS is in the AC normal mode, press and hold the On/Off/
Test button until the alarm sounds four beeps, and then release. The
UPS will perform a 10-second battery test.
When the unit is operating in Battery mode, pressing the Alarm Si-
lencer Button will silence the audible alarm. Once the UPS reaches
the LBW (Low Battery Warning) threshold the alarm will be re-activated.
The alarm cannot be silenced during the LBW alarm or any Fault alarms.
Once the UPS transfers to the AC mode the alarm will be reset to de-
fault.
The Scroll Button allows the user to scroll through the UPS parameters
that are available on the LCD screen.
Description
Message
When the amount of load attached to the UPS is
>
106% of its power
rating; the Overload icon will flash Off and On, all of the LEDs in the
Load Level Bar Graph will be illuminated and the UPS will sound a
constant alarm to indicate that there is an Overload condition.
The UPS reports the following parameters on the LCD screen:
Input:
Voltage, Frequency
Output:
Voltage, Frequency, KVA (Apparent power), KW (Active power)
Runtime:
The time operating on the Battery mode in minutes