![Minebea CSD-581-15 Instruction Manual Download Page 39](http://html.mh-extra.com/html/minebea/csd-581-15/csd-581-15_instruction-manual_1801110039.webp)
19
4−3−4. Connection with power supply and ground
Connection with power supply and ground should be made as follows:
Besides, grounding should be the D class with single ground.
Power supply voltage
DC24 V (DC18 V to DC36 V)
Power consumption
Approx. 9 W at maximum (At DC24 V)
DC24 V
(DC18 V to 36 V)
DC24 V
(DC18 V to 36 V)
Enlarged figure for
connecting section
D class single ground
D class single ground
Warning
●
Connection with power supply and ground should be made securely
as the figure indicates, and also should be made within the specified
condition of power supply. If neglected, it may cause an unexpected
failure.
●
Grounding for the instrument should be the D class with single
ground. If neglected, it may cause an unexpected malfunction due to
the effects of noise from another equipments.
●
GND terminal (Terminals 1 : Terminal No.3) and land (F.G.) at the
installation hole for P.C. board of the instrument have connected on
the pattern of P.C. board .
CN202
DIP202 DIP203