8
Installation
Limit switch connections (optional)
All connections to the logic
board are prewired (see prewired
connections on page 29). If your
application requires the use of limit
switches, connect the limit switches
to the logic board as shown in
Figure 6. If only the forward limit
switch is used, remove the reverse limit switch and jumper terminal 21 to
22. If only the reverse limit switch is used, remove the forward limit
switch and jumper terminal 20 to 22.
Remote pushbuttons
(optional)
Add external jog, stop, reverse
and forward pushbuttons to control
the drive from a remote location.
Connect normally open pushbuttons
to top board terminals 15 through 19
(see Figure 7). Case pushbuttons
may still be used if external
pushbuttons are connected.
Figure 6. Optional limit switch
connections
Figure 7. Optional remote pushbutton
connections
Field output
The field output is for shunt wound motors only. Do not make any
connections to the field output when using a permanent magnet motor.
See Table 2 for field output connections.
Table 2. Field Output Connections
Line Voltage
Approximate Field
Field
(VAC)
Voltage (VDC)
Connections
115
50
F1 and L1
115
100
F1 and F2
230
100
F1 and L1
230
200
F1 and F2
250-0234 rev 1.qxd 3/12/99 11:14 AM Page 8
Summary of Contents for RG501A
Page 8: ...vi 250 0234 rev 1 qxd 3 12 99 11 14 AM Page vi...
Page 10: ...2 Dimensions Figure 1 RG501A and RG511A Dimensions 250 0234 rev 1 qxd 3 12 99 11 14 AM Page 2...
Page 41: ...33 Notes 250 0234 rev 1 qxd 3 12 99 11 14 AM Page 33...
Page 42: ...34 Notes 250 0234 rev 1 qxd 3 12 99 11 14 AM Page 34...