background image

Fcontrol

FXDM

Frequency inverter with integrated sine 

lter for 3 ~ fans

Quick Start Guide

Detailed Description on www.ziehl-abegg.com

Software version: D1333A from Version 2.37

L-BAL-E223-GB 1623 Index 003

Part.-No. 00153236

english

CZ

|

D

|

DK

|

E

|

F

|

FIN

|

GB

|

I

|

NL

|

P

|

PL

|

RU

|

S

|

 

 www.ziehl

­

abegg.com

Summary of Contents for FXDM series

Page 1: ...egrated sine lter for 3 fans Quick Start Guide Detailed Description on www ziehl abegg com Software version D1333A from Version 2 37 L BAL E223 GB 1623 Index 003 Part No 00153236 english CZ D DK E F F...

Page 2: ...up 12 6 1 Jumper for the input signal 12 6 1 1 External Setpoint External speed setting in manual operation 12 6 2 Select operation mode 13 7 Start up 14 7 1 Prerequisites for commissioning 14 7 2 Pro...

Page 3: ...ety instructions 2 1 Intended use The equipment is to be used solely for the purposes speci ed and con rmed in the order Any other use above and beyond this is considered not for the intended purpose...

Page 4: ...ue to faults It is only permitted to remove the housing cover after waiting for 3 minutes once the line supply cable has been shut down Should measurement or adjustment work be unavoidable on the open...

Page 5: ...ssible shipping damage Start up is not allowed in the case of transport damage At a weight greater than 25 kg for men 10 kg for women the device should be lifted out by two persons according to REFA T...

Page 6: ...ondingly larger clear ance or thermal shielding is required 4 3 Fastening the device The type of fastening and the number of fastening points are dependent on the housing design All the fastening poin...

Page 7: ...ning at 8 points GM00002A_M 15 12 2015 1 7 2 3 4 5 6 8 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws...

Page 8: ...cable inlet for cable glands Metal sheet housings are supplied with stoppers Any cable ducts openings not used must be sealed Strip and insert the cables properly Attach cover for terminal compartment...

Page 9: ...ective ground must be made double in accordance with EN 50178 Point 5 2 11and 5 3 2 1 up to a cross section of at least 10 mm For an installation of r c d protection it shall be observed that this mus...

Page 10: ...erminals TB TP have to be bridged Motor fault Motor fault When a connected thermostat or thermistor responds interruption between the two terminals TB TP the device switches off and does not switch ba...

Page 11: ...selection Mode GND A D B D RS 485 MODBUS Interface for networking via MODBUS RTU A D must always be connected to A D of the next devices the same applies to B D In addition a GND connection must be e...

Page 12: ...guration in base setup For Potentiometer Analog Out1 terminal A program to function 1A 10 V like factory setting see IO Setup If a second sensor is connected at input 2 external Setpoint or speed sett...

Page 13: ...02 Sensor TF E2 Temperature control depending on outdoor temperature preset set point 5 0 C P band 20 0 K 2 03 Sensor TF E1 Temperature control with additional functions shutter and heating 2 04 1x S...

Page 14: ...5 Menu group Start Set the menu language if necessary factory setting English Language GB 6 Menu group Base setup Setting the desired operation Mode factory setting 1 01 Speed controller see Selectio...

Page 15: ...MotorRa tedVolt OTM 00010 56 11 GB Lan guage 8 W Input power 0 0 Hz Min Speed 2 ext Fault OFF E2 Func tion OFF Save User Setup 10 0 V A max Level max 48 5 Hz Edgefre quency 585 V DC Voltage OFF Reset...

Page 16: ...3 gures display unit etc 12 Text line 16 gures display text menu P Program key and open menu Menu selection reduce value Menu selection increase value ESC key combination Escape leave menu 8 2 Menu op...

Page 17: ...In order to simplify the initial start up operation the service level is enabled at rst I e not protected by the PIN 0010 see Controller Setup PIN protection OFF If PIN protection is activated ON the...

Page 18: ...6 8 7 54 FXDM14M 308143 14 13 5 12 3 40 16 310 54 6 8 5 54 FXDM18AM 308174 18 16 7 15 5 40 20 400 9 1 54 FXDM18M 308173 18 16 7 15 5 40 20 400 8 9 54 FXDM22AM 308108 22 19 2 17 7 40 25 520 14 5 54 FX...

Page 19: ...for 4 20 mA input Ri 100 Voltage supply e g for sensors 24 V 20 Imax 120 mA for connection to an external AXG terminal minus approx 50 mA Output 0 10 V Imax 10 mA short circuit proof Digital inputs D...

Page 20: ...issible temperature for the rated current at rated voltage is speci ed as rated temperature Since the dissipation of the power loss heat development in the device is decisively dependent on the ambien...

Page 21: ...Normal 7 M 3 U V W PE TB Y q 3 Motor mit eingebauten Thermostatschaltern with internal thermostats 3 TB C 24V GND MODBUS RS 485 GND 24 V A D B D A D GND Terminal AXG 1A E B D 1 Line 3 208 480 V 50 60...

Page 22: ...technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries ou...

Reviews: