PELLERIN MILNOR CORPORATION
BIPDUI01 (Published) Book specs- Dates: 20080723 / 20080723 / 20080723 Lang: ENG01 Applic: PD6
Service Connections For Gas, Steam and Hot Oil Dryers,
Conditioners and Shakers
1.
General
The connections which may be required depending on machine model and options are:
1. Piped Inlets and Outlets: cold water, compressed air, gas, steam, hot oil, steam condensate
line or gas line vent, main air intake, main air exhaust. The sizes and locations of piped inlets
and outlets are shown on the dimensional drawing for your machine.
2. Electric Power Connections.
3. Electrical Control Connections.
2.
Precautions for Piped Connections
1. Inlet pressure must be within the range specified. Pressure outside of the range may cause the
machine to operate inefficiently or to malfunction and may damage machine components.
2. When connecting water and steam inlets, always install unions and shut off valves at the
point of connection to permit removal of the machine components for servicing, if necessary.
3. A vent line must be installed from the regulator vent to the outdoors (if applicable).
4. A minimum 1/2 inch NPT plugged tapping, accessible for test gauge connection, must be
installed immediately upstream of the gas supply connections to the dryer (if applicable).
WARNING 1 : Explosion and Fire Hazards
—Improperly installed gas-fired devices have
the potential for gas release.
• Conform with local codes or, in their absence, with the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54
or the
Natural Gas and Propane Installation Code, CSA B149.1
or a
superseding directive.
• The machine must be electrically grounded in accordance with local codes or, in their
absence, with the
National Electric Code, ANSI/NFPA 70
or the
Canadian Electrical
Code, CSA C22.1
or a superseding directive.
WARNING 2 : Explosion, Fire, and Machine Damage Hazards
—Gas pressure in excess
of 1/2 psi (3.5 kPa) can damage gas train components, possibly resulting in the release of gas.
• Disconnect the dryer and its manually operated appliance main gas valve from the gas
supply for any pressure testing of that system at pressures in excess of 1/2 psi (3.5 kPa).
• Isolate the dryer from the gas supply by closing the equipment shutoff valve during any
pressure testing of that system at pressures equal to or less than 1/2 psi (3.5 kPa).
CAUTION 3 : Machine Malfunction Hazard
—Steam traps rated at 85 to 180 psi (586 to
1241 kPa) will not operate properly below 60 psi (414 kPa). Steam traps rated at 160 to 225 psi
(1103 to 1551 kPa) will not operate properly below 115 psi (793 kPa).
• Conform to the rated pressure of the steam coil as stated on the machine nameplate.
• Choose a steam trap with a pressure rating corresponding to the actual pressure supplied.
CAUTION 4 : Machine Damage Hazards (Steam Dryers and Conditioners Only)
—
Allow steam coil to preheat and purge condensate before operating dryer or conditioner.
• Verify that the facility boiler has operated at least 15 minutes before the dryer receives the
42
Summary of Contents for 7272TG1L
Page 6: ......
Page 8: ...2 ...
Page 46: ...40 ...
Page 47: ...Section 1 Service and Maintenance 41 ...
Page 103: ...Section 2 Drive Assemblies 97 ...
Page 131: ...Section 3 Gas Assemblies 125 ...
Page 148: ...142 ...
Page 149: ...Section 4 Steam Assemblies 143 ...
Page 155: ...Section 5 Pneumatics 149 ...
Page 166: ...160 ...
Page 167: ...Section 6 Door Assemblies 161 ...
Page 176: ...170 ...
Page 177: ...Section 7 Water Assemblies 171 ...
Page 182: ...176 ...
Page 183: ...Section 8 Installation Drawings 177 ...
Page 184: ...178 ...
Page 185: ...179 ...
Page 186: ...180 ...
Page 187: ...181 ...
Page 188: ...182 ...
Page 189: ...183 ...
Page 190: ...184 ...
Page 191: ...185 ...
Page 192: ...186 ...
Page 193: ...187 ...
Page 194: ...188 ...
Page 195: ...189 ...
Page 196: ...190 ...
Page 197: ...191 ...
Page 198: ...192 ...
Page 199: ...193 ...
Page 200: ...194 ...
Page 201: ...195 ...
Page 202: ...196 ...
Page 203: ...197 ...
Page 204: ...198 ...
Page 205: ...199 ...
Page 206: ...200 ...