![Milltronics OCM II PL-269 Instruction Manual Download Page 47](http://html1.mh-extra.com/html/milltronics/ocm-ii-pl-269/ocm-ii-pl-269_instruction-manual_1797001047.webp)
P2=2
BS-3680 TRAPEZOIDAL THROATED FLUME
U0 = Q
cal
The flowrate at full head
enter:
[value from specs.]
U1 = t
cal
The time units of Q
cal
enter:
[0] per second
[1] per minute
[2] per hour
[3] per day
U2 = h
cal
The head at which Q
cal
occurs
enter:
[value from specs.]
U3 = b
Width of flume throat
enter:
[value from specs.]
U4 = B
Width of approach channel
enter:
[value from specs.]
U5 = p
Height of hump
enter:
[value from specs.]
U6 = L
Length of prismatic section of the contraction
enter:
[value from specs.]
U7 = m
Side slope (m horizontal : 1 vertical)
enter:
[value from specs.]
VALUES CALCULATED BY OCM II
U8 = Cv
Velocity coefficient at current head
U9 = Cd
Discharge coefficient at current head
U10= Cs
Shape of coefficient at current head
U11= A
Area of cross section of flow in approach channel
U12= Cv
cal
Velocity coefficient at h
cal
U13= Cd
cal
Discharge coefficient at h
cal
U14= Cs
cal
Shape coefficient at h
cal
U15= h
The liquid head
U16= eta
A numerical coefficient which varies with m
Flowrate is given by:
Q = Q
cal
x Cv/Cv
cal
x Cd/Cd
cal
x Cs/Cs
cal
x (h/h
cal
)
1.5
PL-269
7 – 19
Summary of Contents for OCM II PL-269
Page 6: ......
Page 8: ......
Page 12: ......
Page 22: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 76: ......
Page 78: ......
Page 92: ...PL 269 9 14 ...
Page 94: ......
Page 95: ......
Page 106: ......