The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
9
3.3.2
Exiting the SETUP mode
• press the
key (the SET EEP message will be displayed, and at the
same time configuration parameters will be stored in memory).
3.4 The MEASURE Mode
This mode permits to preset for individual channels the measure of displayed / controlled
physical quantity, e.g. (°C, bar, %, etc.), which will be displayed in the measure display
field. In order to switch to the MEASURE [WYMIAR] mode, select the F01 special
function:
• then (as appropriate for a selected channel) set the measure of the measured /
controlled quantity by pressing the
key.
Follow the sequence below in order to change the display
°C
%
Bar
DISPLAY OFF
1
2
3
4
5
6
7
8
9
10
11
12
Attention! The above applies only to standard version of the Recorder.
3.4.1
Exiting the MEASURE mode
•
press the
key (the SET EEP message will be displayed, and at the
same time configuration parameters will be stored in memory).
3.5
MEASUREMENT CHANNEL SCALING, THE -SERVICE- MODE
ATTENTION: Prior to commencement of measurement channel tuning, check
whether location of switches defining type of input is in compliance with guidelines...!
In order to scale (set zero and amplify) indications in individual measurement channels it
is necessary to switch to the SERVICE mode by selecting the F02 special function.
The following information will be displayed after selecting this function :
• readout from the AC converter in the real-time clock display field
• letters
ch.
and measurement channel number in channel no. 1 display field
• readout value in units matching the configuration (in channel no. 2 display field)