The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
3
TECHNICAL DATA
DIMENSIONS:
•
assembly hole size: 142+1mm X 237+1mm
•
assembly depth including terminals: 55mm
•
outside dimensions: 265x152
WEIGHT:
•
1250 g (RECORDER)
•
800 g (TRANSFORMER)
POWER SUPPLY:
•
~24V(AC), 220-24V TRANSFORMER INCLUDED IN THE SET
STRUCTURE:
•
SINGLE ELEMENT, “FRONT PANEL”-TYPE
PROTECTION CLASS:
(ACCORDING TO IEC 529)
•
from terminal side: IP 20
•
from front side: IP 65
HUMIDITY:
•
0..75 % (OF RELATIVE HUMIDITY)
TEMPERATURE:
•
ambient: -20..+70 °C
•
working: 0..+60 °C
OUTPUTS:
•
max 12 RELAY OUTPUTS 250V,
TOTAL
CURRENT INTENSITY OF CONNECTED RELAYS: Icmax=4A
•
4 TRANSISTOR OUTPUTS, Iomax=100mA (optionally)
INPUTS:
• 8 MEASUREMENT CHANNELS WITH INPUT
- PT-100 - MEASUREMENT RANGE FROM -100.0°C TO +400.0°C,
RESOLUTION (ACCURACY) 0.1°C
- CURRENT SIGNAL: 0..20 mA , 4..20 mA (RANGE: 3 DIGITS)
• BINARY CONTROL INPUT: 0-220V AC (0-24 V AC)
DIGITAL COMMUNICATION:
• SERIAL PORT
1xRS-232
(PRINTER)
1xRS-485 (MASTER COMPUTER)
RECORDING MEMORY:
• 2000 samples / channel for RAM memory = 32KB (STANDARD)