![Mikster DLM-080 User Manual Download Page 44](http://html1.mh-extra.com/html/mikster/dlm-080/dlm-080_user-manual_1794732044.webp)
The DLM-080 FUTURE Digital Recorder – User’s Manual
26.11.2004
44
(according to algorithm 3)
024Dh F47
0..2
Controller output definition for CHANNEL 2
as before
024Eh F48
0..2
Controller output definition for CHANNEL 3
as before
024Fh F49
0..2
Controller output definition for CHANNEL 4
as before
0250h F50
0..1
Controller output definition for CHANNEL 5
F50=0 controller contact normally
closed (algorithm 1)
F50=1 controller contact normally
open (algorithm 2)
0251h F51
0..1
Controller output definition for CHANNEL 6
as before
0252h F52
0..1
Controller output definition for CHANNEL 7
as before
0253h F53
0..1
Controller output definition for CHANNEL 8
as before
0254h F54
0..13
Analogue input type definition and display
range definition for CHANNEL 1
Definition:
0 – PT-100 RANGE: (-
99,0..400,0); 1
– RANGE OF HUMIDITY FROM
PSYCHROMETER: 0..99
2 – NOT USED
3 – RANGE 0,00..9,99 (0..20mA)
4 – RANGE 00,0..99,9
(0..20mA)
5 – RANGE 000..999
(0..20mA)
6 – RANGE 0,00..9,99
(4..20mA)
7 – RANGE 00,0..99,9
(4..20mA)
8 – RANGE 000..999
(4..20mA)
9 – NOT USED
10 – NOT USED
11 – TIME RANGE: 0..999
SECONDS (forward counting)
12 – TIME RANGE: 0..999
MINUTES (forward counting)
13 – TIME RANGE: 0..999
HOURS (forward counting)
0255h F55
0..13
Analogue input type definition and display
range definition for CHANNEL 2
as before
0256h F56
0..13
Analogue input type definition and display
range definition for CHANNEL 3
as before
0257h F57
0..13
Analogue input type definition and display
range definition for CHANNEL 4
as before
0258h F58
0..13
Analogue input type definition and display
range definition for CHANNEL 5
as before
0259h F59
0..13
Analogue input type definition and display
range definition for CHANNEL 6
as before
025Ah F60
0..13
Analogue input type definition and display
range definition for CHANNEL 7
as before
025Bh F61
0..13
Analogue input type definition and display
range definition for CHANNEL 8
as before
025Ch F62
0..2
Procedure of operation for CHANNEL 1
defined as time-meter (F38)
0 – time-meter initiating
(PROG+2seconds)