remove the flow limiter and
clean it
29
Heat exchanger is blocked
Remove the heat exchanger
from the unit by releasing the
mounting springs (2) and the
clamp at the front. Use
pressurised air to blow the
exchanger clean; if necessary,
rinse with a slightly (10%)
hydrochloric acid solution
30
High limit thermostat defective
Replace the maximum
thermostat
31
Maximum load is too high
Check the minimum setting of
the unit and the nozzle for a
proper diameter.
32
Incorrect nozzle
Replace by correct nozzle
33
Flue gas thermostat defective
Replace
34
Controller defective
Replace entire boiler control
box
35
Ignition electrode incorrect
Replace
36
Moisture on gas valve cables
Dry, if necessary using hot air
(hair dryer) and check for
proper functioning; replace if
necessary
37
Moisture on electronics box
See 36
38
Moisture in pump wiring
See 36
39
Moisture on fan or and/or
connections
Remove the connection and
dry by blowing or using hair
dryer
40
Fan connector incorrectly
connected
Connector must point in the
direction of the outside of the
ventilator and one side must
fit into the slot in the printed
circuit
41
Connector incorrectly
connected
Check connectors and fit into
one another properly
42
Cable damaged
Check cables for possible
damage or kinks
43
Sensor defective
Check cable pipe connections
44
Flue gas re-circulation from
behind heat exchanger
Check heat exchanger seal on
flue gas box, replace if
necessary.