Page 44 Mikrofill (uk) ltd.
Room temperature controlled without mixing valve
Function No.
Room Temp
Control
Max Flow
Temperature
54
RE 2132
55°C
55
RE 2132
70°C
56
RE 2132
85°C
57
240v Room Stat
55°C
58
240v Room Stat
70°C
59
240v Room Stat
85°C
Room temperature controlled with mixing valve
Function No.
Room Temp
Control
Max Flow
Temperature
60
With two RE 2132
70°C primary
61
With two RE 2132
85°C primary
62
With one RE 2132
70°C primary
63
With one RE 2132
85°C primary
64
240v Room Stat
70°C
primary
65
240v Room Stat
85°C
primary
Without room unit, thermostat or outside temperature control, constant flow temperatures
without a mixing or secondary circuit.
Function No.
Room Temp
Control
Max Flow
Temperature
66
None
55°C
67
None
70°C
68
None
85°C
Without room unit, thermostat or outside temperature control, constant flow temperatures
with a mixing or secondary circuit.
Function No.
Room Temp
Control
Max Flow
Temperature
69
None
70°C primary
70
None
85°C primary
Mikrofill cascade manager KKM2 Settings (for controlling up to nine boilers)
Function No.
Cascade manager
Max Flow
Temperature
71
KKM2
CH temp on KKM2