Flooded type water cooled screw chiller (MIC)
MCAC-CTSM-2018-1
38
Number of steps for valve closing
3970
Valve rate
250
Low SH protection: threshold
1
Low SH protection: integration time
2.5
LOP protection: threshold
-50
LOP protection: integration time
4
MOP protection: threshold
50
MOP protection: integration time
10
Low overheat degree alarm delay
(Low SH, 0 = no alarm)
300
Low evaporation temperature alarm
delay (LOP, 0 = no alarm)
300
High evaporation temperature alarm
delay (MOP, 0 = no alarm)
600
Low air suction temperature alarm
threshold
-50
Low air suction temperature alarm
delay (0 = no alarm)
300