VIII.Troubleshooting
1. Protection items
Midea screw chiller has many protection measures and devices. There
’re many features to aid in
troubleshooting. By using the alarm information, DI/O, AI/O and operating conditions of the chiller during
chiller operation, it
’s convenient to find the possible problem. Verify that the chiller is properly configured,
including options and/or accessories.
Protection items:
Protection
Purpose
High pressure / low pressure
protection of compressor
Ensures the compressor runs in a normal range and
guarantees its service life.
Converse phase, lack of phase
protection
Protects the compressor from damage because of a
converse phase or lack of phase of power.
Anti-freezing protection during
refrigeration
Protects key components such as the evaporator,
condenser and water pipe from damage because of
the expansion caused by water freeing into ice
Overload protection
Protects the compressor from burning due to overload
running.
Over current protection on the compressor
Protects the compressor from burning due to over
current running under bad conditions.
Internal protection
Enables the compressor to run safely under permitted
conditions.
Anti-overheating protection of the system
Protects the compressor from burning because of
running a lack of refrigerant or lubricating oil.
Water flow switch protection
Protects the compressor and the water pump motor
from burning because there is lack of cooling water or
chilled water.
Protection of the sensor fault
Ensures the data from the sensor is correct to prevent
the system from wrong action.
Oil level and oil pressure difference protection
Ensures the compressor can run normally.
High discharge temperature protection
Enables the compressor to run safely under permitted
conditions.
Phase reversal/phase loss (phase protection)
Power supply A/B/C should exist simultaneously and differ from each other by a 120° phase angle.
If not, Phase reversal or phase loss fault will occur and be displayed on screen. Before the unit
starts when phase reversal or phase loss fault occurs, the chiller won
’t start; when Phase reversal or
phase loss fault occurs during chiller operations, the chiller will stop according to the protective stop
program. Both compressors are shut down and water pumps and cooling tower fans stop in
accordance with normal shutdown procedures. When the fault record is cleared and both
temperature and time conditions are satisfied, the chiller can restart.
Water flow failure (both chilled water and cooling water)
PCB controller begins to detect chilled/cooling a water flow switch after the water pumps get
energized 180s. The switch will disconnect if water flow is less than a set point and the water flow
loss signal will occur if it lasts for more than 5s. During chiller operations (including dual heads unit),
any flow switch that disconnects for 5s continuously, Unit stops according to protective stop
program.