Flooded type water cooled screw chiller (MIC)
MCAC-CTSM-2018-1
72
Foundation Bolt Installation Dimension Table
3) Vibration isolators
Put the absorbers under unit saddles before finally positioning the unit. The quantity of absorbers
used for each unit is decided by the elasticity or durometer value of the absorber. Refer to the typical
isolation pad and vibration isolator below during selection.
Typical isolation pad
Typical vibration Isolator
≥
Expected load bearing values are listed below:
Model
Isolation pad
Vibration Isolator
Running
weight(kg)
Minimum load
bearing (kg/EA)
Minimum
Quantity
Minimum load
bearing (kg/EA)
Quantity
LSBLG340/MCF
900
4
900
4
2515
LSBLG440/MCF
1000
4
1000
4
2560
LSBLG540/MCF
1200
4
1200
4
2935
LSBLG720/MCF
1400
4
1400
4
3800
LSBLG805/MCF
1800
4
1800
4
4210
LSBLG890/MCF
1800
4
1800
4
4300
LSBLG1055/MCF
2000
4
2000
4
5470
LSBLG1200/MCF
2200
4
2200
4
6482
LSBLG1300/MCF
2200
4
2200
4
6582
LSBLG1410/MCF
2200
4
2200
4
6680
LSBLG1620/MCF
2200
4
2200
4
8250
LSBLG1780/MCF
2200
4
2200
4
8400
Model
Dimension
LSBLG***/MCF
340
440
540
720
805
890
1055 1200
1300 1410
1620 1780
D(mm)
2850 2850
2850
2850
2850
2850
2850 3850
3850 3850
3850 3850
E(mm)
1100
1100
1100
1300
1300
1300
1400 1400
1400 1400
1500 1500