27
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Condition
Temp. Time
Compressor Outdoor
fan
T> TE6
On
On
Evaporator
Temp. up
T< TE6
>5 Minutes
Off
Off
T> TE5
On
On
Evaporator
Temp. down
T< TE5
>5 Minutes
Off
Off
8.7 Dehumidifying
mode
8.7.1
The 4-way valve is off in dehumidifying mode
8.7.2
Compressor and Indoor Fan actions in dehumidifying mode
NO
Conditions
Indoor Fan
Compressor and Outdoor Fan
1 TA
≥
TS+2
LOW
BREEZE
ON 6minutes
OFF 4minutes
2 TS
≤
TA<TS+2
LOW
BREEZE
ON 5minutes
OFF 5minutes
3 TA
<
TS
LOW
BREEZE
ON 4minutes
OFF 6minutes
Repeat on and off cycle.
Downloaded from AC-Manual.com Manuals